Moog ACV with CANopen bus interface
7 Servo valve functions
Monitoring
B99224-DV018-D-211, Rev. A, October 2018
236
7.15.2.2 Object 0x63D2: Delay time
The delay time defines the minimal duration of a control deviation before a fault is active. The Time is set to
zero if the position is inside the window, if the fault is acknowledged or if one of the following parameters is
changed: <Type> (0x63D1), <UpperThreshold> (0x63D4), <LowerThreshold> (0x63D5) or
<DelayTime> (0x63D2).
Chapter "2.4.3 Units and prefix parameter", page 12
7.15.2.3 Object 0x63D4: Upper threshold
This parameter defines the upper threshold of the control deviation's tolerance band.
Chapter "2.4.3 Units and prefix parameter", page 12
7.15.2.4 Object 0x63D5: Lower threshold
This parameter defines the lower threshold of the control deviation's tolerance band.
Chapter "2.4.3 Units and prefix parameter", page 12
ValvePressureControl_ControlMonitoring
Index
Sub-index
Parameter name
Data type
Access
Persistence
Value range
Default
0x63D2
1
DelayTime
UINT16
rw
Y
UINT16
30
0x63D2
2
Unit
UINT8
ro
-
UINT8
3
0x63D2
3
Prefix
INT8
ro
-
INT8
–3
ValvePressureControl_ControlMonitoring
Index
Sub-index
Parameter name
Data type
Access
Persistence
Value range
Default
0x63D4
1
UpperThreshold
INT16
rw
Y
INT16
512
0x63D4
2
Unit
UINT8
ro
-
UINT8
0
0x63D4
3
Prefix
INT8
ro
-
INT8
0
ValvePressureControl_ControlMonitoring
Index
Sub-index
Parameter name
Data type
Access
Persistence
Value range
Default
0x63D5
1
LowerThreshold
INT16
rw
Y
INT16
–512
0x63D5
2
Unit
UINT8
ro
-
UINT8
0
0x63D5
3
Prefix
INT8
ro
-
INT8
0