L38DF-ST See-thru Indoor Gas Fireplace

Part No. XG0810 - 092109

f i r e    f e a t u r e 

 

                   

                       

 

Amendment

 

 

 

  (Gas Fireplace / Equipment sold in the State of Massachusetts)

 

 

 

 

   5.08: Modifications to NFPA-54, Chapter 10

 

(1) Revise NFPA-54 section 10.5.4.2

 

by adding a second exception as follows:

Existing chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manually reset device 

that will automatically shut off the gas to the burner in the event of a sustained back-draft

.

 

(2) Revise 10.8.3

 by 

adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, 

including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in 

the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 

 

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.

 

At the time of installation of the side wall horizontal vented gas fueled equip-

ment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor 

level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon 

monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled 

equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon 

monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with 

alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days 

to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm 

shall be installed.

 

2. APPROVED CARBON MONOXIDE DETECTORS.

 

Each carbon monoxide detector as required in accordance with the above provisions 

shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified. 

 

3. SIGNAGE.

 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet 

above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print 

size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

 

4. INSPECTION.

 The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, 

upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. 

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 

 

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the 

Board; and 

 

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or struc-

ture used in whole or in part for residential purposes.  

 

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED

. When the manufacturer of Product 

Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions 

provided by the manufacturer for installation of the equipment and the venting system shall include:

 

1. Detailed instructions for the installation of the venting system design or the venting system components; and

 

2. A complete parts list for the venting system design or venting system. 

 

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

. When the manufacturer of a Prod-

uct Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, 

the following requirements shall be satisfied by the manufacturer:

 

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and 

 

2. The “special venting systems”

 shall be Product Approved by the Board, and the instructions for that system shall include a parts list and 

detailed installation instructions. 

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for 

venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

 

(3) After NFPA-54 section 10.10.4.2

 add a new section 10.10.4.3 as follows:

When more than four gas appliances are to be vented through a common gas vent or common horizontal vent manifold, a plan of the proposed vent installation 

shall be submitted to the Inspector and the serving gas supplier for review and approval.

Extraction from: Massachusets Rules and Regulations

5.00: Amendments To 2002 Edition Of ANSI Z223.1-NFPA-54

Appendix B - State of  Massachusetts

Содержание L38DF-ST series

Страница 1: ...enancecancause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier Warning What to do if you smell...

Страница 2: ...gas fireplace will give you years of durable reliable use Welcome to the FireFeature family of gas fireplace products Safety Alert Key DANGER Indicates a hazardous situation which if not avoided will...

Страница 3: ...manufactured or approved by Montigo in combination with this Montigo fireplace system Installation other than as instructed in this manual Consult your local Gas Inspection Branch on installation requ...

Страница 4: ...e to unprotected combustible walls which are perpendicular to the fireplace opening must not project beyond the shaded area shown in Figure 24 For protection against freezing temperatures it is recomm...

Страница 5: ...lation This section covers the installation of direct venting and terminations Installation Requirements Q Q L38DF ST model fireplaces are certified for use with Montigo Standard Series 5 8 venting co...

Страница 6: ...the top of the termination where temperatures are highest 2 Attach to the faceplate of the termination using four sheet metal screws 3 IfinstallingtheterminationoverVinylsiding UsetheVSSTermination s...

Страница 7: ...its set by the venting graph see Figure 7 Figure 8 Retracted Installation using a combination of solid and flex venting Use the vent graph to determine your allowable run then select appropriate compo...

Страница 8: ...tics will change if the maximum vent height is used Minimum clearances 2 from vent to all combustible materials must be maintained Amaximum of two offsets each offset has two 90 bends may be made and...

Страница 9: ...tallation CAUTION The Installation shown in Figure 12 only 5 8 PEXT Vent to be used Power Vent models LDVPV47 EDVRSPV58 and EDVWSPV58 to be used within the shaded area of graph See Index of this guide...

Страница 10: ...ions may be used in conjunction with one another to obtain different possible horizontal length instal lations NOTE Flex section must not exceed maximum horizontal length of 3 feet and for this applic...

Страница 11: ...Power Vent Module document XG0750 EDVRSPV47 Exterior Vertical Roof mount 4 7 stainless steel Power Vent system document XG1303 EDVWSPV47 Exterior Horizontal Wall mount 4 7 stainless steel Power Vent s...

Страница 12: ...valent Figure 27a Wiring schematic for optional fans G L2 WH L1 BLK p g Quick Connect lu to motor WARNING We recommend careful consideration be given to the effects of elevated mantel temperatures whi...

Страница 13: ...aintenance or cleaning Install in reverse order Installed Gas Valve Cover Finger Holes Remove the Horizontal Access Panel To install the door hook the top edge of the door frame into place Lower thedo...

Страница 14: ...ure 29b Spreading designer beads evenly Propane L38DF ST fireplace have the option of installing the optional cultured rocks or designer glass beads As described below Propane gas the designer beads o...

Страница 15: ...ollow the gas supplier s instructions To Turn Off Gas To Appliance 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Replace the lower Horizontal access panel 1 Turn off rem...

Страница 16: ...Page 16 L38DF ST See thru Indoor Gas Fireplace Part No XG0810 092109 f i r e f e a t u r e Operation...

Страница 17: ...Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instru...

Страница 18: ...nob marked Hi Lo in the centre of the gas control valve See Figure 32 The front burners are not adjustable Q Q To raise the flame height turn the black knob located behind the lower trim counter clock...

Страница 19: ...until the bubbling stops completely Figure 34 Pilot Burner Troubleshooting The following is a troubleshooting chart of possible problems PROBLEM CORRECTIVE ACTION Noisy Pilot Flame Locate pilot adjus...

Страница 20: ...1152 Oriface LPG Oriface NG L38DF ST I RGC1004 RGC1003 RPA003 RPA004 ROR1151 ROR1152 RDTL38 L38DF ST A RGC3033 RGC3034 RPA052 RPA053 ROR1151 ROR1152 RDTL38 Troubleshooting Follow this information to r...

Страница 21: ...ust be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance wi...

Страница 22: ...tlet 3 feet minimum in the United States 6 feet 1 8 m minimum in Canada L clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm mi...

Страница 23: ...above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in si...

Страница 24: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0810 092109 f i r e f e a t u r e...

Отзывы: