Page 4
L38DF-ST See-thru Indoor Gas Fireplace
Part No. XG0810 - 092109
f i r e f e a t u r e
Installation
Installing The Fireplace Shell
The
L38DF-ST fireplace may be installed in any location that main
-
tains proper clearances to air conditioning ducts, electrical wiring and
plumbing. Safety, as well as efficiency of operation, must be considered
when selecting the fireplace location. Try to select a location that does
not interfere with room traffic, has adequate ventilation, and offers an
accessible pathway for Direct Vent installation. Refer to page 4 -
Vent
Installation
for more information.
The fireplace dimensions are shown below:
When installing a shelf over the top of the fireplace, the following guidelines
must be adhered to: For Rear Vent applications the minimum clearance from
the top of the
L38DF-ST fireplace to a shelf is 10". For Top Vent applications,
the minimum clearance are shown in the clearance table. (
Minimum
2" clearance must still be maintained around the vent pipes.
)
Figure 2.
Framing dimensions.
Framing
Top View
Front View
Side View
Clearances
These clearances apply to all dimensions
except the framed
opening
, where the clearance to combustibles is
0"
. The
L38DF-ST
clearance to unprotected combustible walls which are perpendicular to
the fireplace opening, must not project beyond the shaded area shown
in
Figure 24
.
For protection against freezing temperatures, it is recommended that
outer walls of the chase be insulated with a vapor barrier. This will reduce
the possibility of a cold-air convection current on the fireplace.
Figure 1.
Fireplace dimensions.
* Clearance from top of the Fireplace to a combustible ceiling within the fireplace
enclosure.
** Refer to Pages, 10 & 11.
17 1/2"
Sides
1"
Floor
0"
Mantle
4"
Top (Top Vent)
L38DF-ST
10"
Top (Rear Vent)
Back
3”
Vent Ring
2"
10
min.
shelf
supplied shield
RHS101
39 1/2 min
17 1/2
min
PEL Short
90 elbow
shelf
supplied shield
RHS101
Figure 2a.
Framing dimensions. (Top Vent)
Figure 2b.
Framing dimensions. (Rear Vent)
WARNING!
When this appliance is installed directly on carpeting, tile or any
combustible material other than wood flooring, it must be installed
on a metal or wood panel extending the full width and depth of
the appliance.
6 1/4”
5 1/4”
18”
29 1/2”
33 3/4”
5”
8”
24”
35 1/4”
opening
1 1/4”
1 1/4”
1 1/4”
1”
37 3/4”
37 3/4”
7”
24”
36 3/8”
8”
5”
26 3/4”
opening
40”
41”
23 3/4”
40”
34 1/2”
Both walls Typical. May
not be exactly as shown.
Notes:
Install supplied metal header (Part
No#L38ST060) above fireplace
after unit is in place. Use supplied
hardware to fasten to framing.
Both sides Typical. Unit may not
be exactly as shown.