L38DF-ST See-thru Indoor Gas Fireplace

Part No. XG0810 - 092109

f i r e    f e a t u r e 

7”

1 3/4”

2 3/8”

1 3/4”

Installation

Installing The Gas Line

The gas line must be installed before completing the installation of the 

L38DF-ST

 Fireplace. 

Natural Gas

 requires a minimum  inlet gas supply  

pressure of 5.5" W.C. & a manifold pressure of 3.5" W.C. Propane 

Gas requires a minimum inlet gas supply pressure of 11" W.C. & a 

manifold pressure of 10" W.C. Provision must also be made for a 1/8" 

N.P.T. plugged tapping and be accessible for test gauge connection 

immediately upstream of the gas supply controls to the appliance. The 

fireplace gas connection and the main operating gas valve is located 

behind the removable trim at the bottom of the unit and need only be 

attached to the gas line  with an approved fitting, as required by the 

applicable installation codes

.

To access the fireplace gas connection the main burner must be 

removed as shown below in figure 5a.

• Only use gas shut-off valves approved for use by the state, province, 

region, or governing body, in which the appliance is being installed, or 

as required by the applicable installation codes.

• Flexible gas connectors must not exceed 3 feet in length, unless it is 

allowable  within applicable installation codes.

Note:

  After gas line is connected, each 

appliance connection

,

 

valve and valve train

 must be checked while under normal 

operating  pressure  with  either  a  liquid  solution,  or  leak 
detection device, to locate any source of leak. Tighten any 
areas  where  bubbling  appears  or  leak  is  detected  until 
bubbling stops completely or leak is no longer detected. 
DO  NOT use a flame of any kind to test for leaks.

Figure 5a.  

Gas line access.

The appliance and its individual shut-off valve must be disconnected 

from the gas supply piping system during any pressure testing of that 

system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by 

closing its individual manual shut-off valve during any pressure testing 

of the gas supply piping system at test pressures equal to or less than 

1/2 psig (3.5 kPa).

Vent  Installation

This section covers the installation of direct venting and terminations. 

Installation Requirements

 

Q

L38DF-ST model fireplaces are certified for use with Montigo Standard 
Series (5" / 8") venting components.

 

Q

Minimum clearance to combustible construction around the vent pipe 
is 1" 
on all sides, except on horizontal venting where the top of the pipe 
must have a clearance of at least 2".

 

Q

Use only 

certified Montigo vent components.

 (Use of other parts will void the 

Montigo warranty, and may impede the operation of the fireplace.)

 

Q

All joints must be secured with a minimum of two screws per joint

 

Q

Vent terminations must not be recessed in walls or siding

 

Q

Horizontal runs must be supported by a minimum of two supports per horizontal 
run. A minimum of one screw on each side of support is also required

 

Q

Flex vent sections may be stretched up to 50% of their total length (eg. a 
24" section may be stretched to 36")

 

Q

Flex vent sections over 6 feet must fall within the limits set by the venting 
graph and must have a minimum vertical rise of 3 inches per foot of flex.

 

Q

Solid vent sections may be cut less than half way from the female end

 

Q

Venting components can be used in any combination of solid/rigid pipe or flex 
pipe and in any orientation (Male connectors can face in any direction)

Installing The Remote Switch

The 

L38DF-ST's 

gas valve is located behind the lower trim, and may 

be connected to a wall switch. The valve generates its own power on

 

a millivolt circuit. Use only low voltage wire, and DO NOT

 connect 

any external power to it.

Note:

  The switch location must not exceed 30' from the fireplace.

Figure 2.  

Back frame dimensions. 

Backframe Min. 37 3/4”

     CAUTION:

  Do not obstruct, or attempt to conceal, the vent termination. 

These actions will affect the operation of the fireplace, and may 
be hazardous.

  In heavy snow areas, take extra care to prevent snow buildup 

from obstructing the vent termination.

     CAUTION!

Due to its high operating temperatures, the appliance should  
be located out of traffic & away from furniture and draperies.

  Children and adults should be alerted to the hazards 

of the high surface temperature, which could cause 
burns or clothing ignition.

  Young children should be carefully supervised when 

they are in the same room as the appliance.

  Clothing or other flammable materials should not be 

placed on or near the appliance.

Содержание L38DF-ST series

Страница 1: ...enancecancause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier Warning What to do if you smell...

Страница 2: ...gas fireplace will give you years of durable reliable use Welcome to the FireFeature family of gas fireplace products Safety Alert Key DANGER Indicates a hazardous situation which if not avoided will...

Страница 3: ...manufactured or approved by Montigo in combination with this Montigo fireplace system Installation other than as instructed in this manual Consult your local Gas Inspection Branch on installation requ...

Страница 4: ...e to unprotected combustible walls which are perpendicular to the fireplace opening must not project beyond the shaded area shown in Figure 24 For protection against freezing temperatures it is recomm...

Страница 5: ...lation This section covers the installation of direct venting and terminations Installation Requirements Q Q L38DF ST model fireplaces are certified for use with Montigo Standard Series 5 8 venting co...

Страница 6: ...the top of the termination where temperatures are highest 2 Attach to the faceplate of the termination using four sheet metal screws 3 IfinstallingtheterminationoverVinylsiding UsetheVSSTermination s...

Страница 7: ...its set by the venting graph see Figure 7 Figure 8 Retracted Installation using a combination of solid and flex venting Use the vent graph to determine your allowable run then select appropriate compo...

Страница 8: ...tics will change if the maximum vent height is used Minimum clearances 2 from vent to all combustible materials must be maintained Amaximum of two offsets each offset has two 90 bends may be made and...

Страница 9: ...tallation CAUTION The Installation shown in Figure 12 only 5 8 PEXT Vent to be used Power Vent models LDVPV47 EDVRSPV58 and EDVWSPV58 to be used within the shaded area of graph See Index of this guide...

Страница 10: ...ions may be used in conjunction with one another to obtain different possible horizontal length instal lations NOTE Flex section must not exceed maximum horizontal length of 3 feet and for this applic...

Страница 11: ...Power Vent Module document XG0750 EDVRSPV47 Exterior Vertical Roof mount 4 7 stainless steel Power Vent system document XG1303 EDVWSPV47 Exterior Horizontal Wall mount 4 7 stainless steel Power Vent s...

Страница 12: ...valent Figure 27a Wiring schematic for optional fans G L2 WH L1 BLK p g Quick Connect lu to motor WARNING We recommend careful consideration be given to the effects of elevated mantel temperatures whi...

Страница 13: ...aintenance or cleaning Install in reverse order Installed Gas Valve Cover Finger Holes Remove the Horizontal Access Panel To install the door hook the top edge of the door frame into place Lower thedo...

Страница 14: ...ure 29b Spreading designer beads evenly Propane L38DF ST fireplace have the option of installing the optional cultured rocks or designer glass beads As described below Propane gas the designer beads o...

Страница 15: ...ollow the gas supplier s instructions To Turn Off Gas To Appliance 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Replace the lower Horizontal access panel 1 Turn off rem...

Страница 16: ...Page 16 L38DF ST See thru Indoor Gas Fireplace Part No XG0810 092109 f i r e f e a t u r e Operation...

Страница 17: ...Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instru...

Страница 18: ...nob marked Hi Lo in the centre of the gas control valve See Figure 32 The front burners are not adjustable Q Q To raise the flame height turn the black knob located behind the lower trim counter clock...

Страница 19: ...until the bubbling stops completely Figure 34 Pilot Burner Troubleshooting The following is a troubleshooting chart of possible problems PROBLEM CORRECTIVE ACTION Noisy Pilot Flame Locate pilot adjus...

Страница 20: ...1152 Oriface LPG Oriface NG L38DF ST I RGC1004 RGC1003 RPA003 RPA004 ROR1151 ROR1152 RDTL38 L38DF ST A RGC3033 RGC3034 RPA052 RPA053 ROR1151 ROR1152 RDTL38 Troubleshooting Follow this information to r...

Страница 21: ...ust be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance wi...

Страница 22: ...tlet 3 feet minimum in the United States 6 feet 1 8 m minimum in Canada L clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm mi...

Страница 23: ...above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in si...

Страница 24: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0810 092109 f i r e f e a t u r e...

Отзывы: