background image

Page 7

 

 
 

4.4.1

 

Latching vs. Non-Latching Limits 

A Latching Limit is one  which, when the alarm trips, remains in this condition regardless of  what the input may do. 
This tripped limit needs to be manually reset by the operator to restore it back to its normal position. Reset is via the 
front panel 

RESET

 button or remotely using Channel 2 Auxiliary input if programmed. A Non-Latching Limit, on the 

other hand, will automatically reset itself when the input no longer exceeds the set point, either high or low. The user 
can program each limit to be Latching or Non-Latching.  Refer to 

Section 5.0

. 

4.4.2

 

Dead band (Hysteresis) 

Dead band is only applicable to 

non-latching limits

.  Dead band is a value that is added to the set point (in the case of a 

low limit) or subtracted from the set point (in the case of a high limit) so that this new value (set point ± dead band) 
becomes  the  reset  point  for  the  alarm.    The  primary  purpose  of  this  function  is  to  prevent  the  alarm  relays  from 
chattering when the input value remains very close to the set point.  Dead band is set in absolute engineering units. For 
example if the Limit is set to 200 RPM as a High limit and the dead band is set to 20 RPM, the alarm will trip when the 
input is greater than 200 but will not reset until the input goes below 180 PM.  Without the dead band feature, the alarm 
relays  would  chatter  on  and  off  it  the  input  varied  from  199  to  201,  which  is  undesirable.    The  user  can  set  the 
hysteresis to any value from 0.0001 to 99,999.  Refer to 

Section 5.0

NOTE:

  The Dead band needs to be less than the setpoint. 

4.4.3

 

Low Limit Lockout  

The Low Limit Lockout is a feature that prevents a low alarm from tripping when the input starts from zero.  The low 
alarm essentially is locked out and will not operate until the input exceeds the low limit, at which time the low alarm is 
enabled and will trip when the input goes below the set point.  This feature enables a motor that has a low speed cut out 
(low alarm) to start from rest  without having to short out the normally closed relay contacts externally.   This  feature 
may be enabled or disabled by the user.  Refer to 

Section 5.0

4.4.4

 

Fail Safe 

The  Fail  Safe  option  reverses  the  sense  of  the  relays,  essentially  energizing  them  under  normal  conditions.  When  an 
alarm is set, the relays will drop out (become de-energized). Thus in the event of a power failure the relays will drop 
out by default creating the equivalent of an alarm condition. 

4.5 

Analog (AO) and Current (IO) Output 

The 

ACT-3X

 has options for voltage (0 to 5Vdc) or current (4 to 20mA) outputs. 

The  analog  outputs  are  derived  from  a  15-bit  digital  to  analog  converter.    This  means  that  the  output  voltage  (or  current) 
changes in steps.  The standard analog output has ~32,000 steps from zero to full scale.  This implies that each step size is 
1/32,000 of the full-scale value or about 0.003% of full scale.  The user can set the actual full scale value anywhere from 1 
to 999,990.  This full-scale value is the value at which the analog outputs are at a maximum, 5 Vdc or 20 mA.  

The zero and full-scale range is usually set to give a reasonable working range for the analog output.  For example, if you 
are measuring the RPM of a motor that typically runs at 1700 RPM, you may want to set the zero scale (offset) for 1000 and 
the full-scale for the analog output at 2000.  Note that the zero and full scale ranges are always set in the units you choose to 
display; RPM in this case.  The output voltage will then be 5 Vdc (20 mA) for an input of 2000. It will be linear between 
1000 (zero scale) and 2000 (full-scale).  Thus, at 1700 RPM the output will be: 

 (1700 - 1000) 
——————   X  5 Vdc = 3.5 Vdc 
 (2000 - 1000) 

 

(2000 - 1000) 

Resolution =    ——————  = 0.03 RPM 
 

32,000 

NOTE:

  For any input below the zero scale setting, the outputs will be at 0 Vdc or 4 mA.  For any input above the full scale 

setting, the outputs will be at their maximum value, 5 Vdc or 20 mA. 

4.6 

Maximum and Minimum 

The unit tracks and saves the maximum and minimum values.  These values are continuously updated and can be viewed at 
any time by pressing the 

RECALL

 button on the front panel.  The first time this button is pressed the 

MAX

imum is shown, 

indicated by the MAX light to the right of the display.  Pressing the 

RECALL

 button a second time shows the 

MIN

imum.  

The  user  can  also  reset  these  values  by  pressing  and  holding  the 

RECALL

  button  and  then  pressing  the 

RESET

  button.  

The next reading will always update both values.  This will keep the minimum value from showing zero unless there was a 
zero reading after the 

RECALL

 and 

RESET

 buttons were pressed. 

Thus, if you start a motor, for example, from zero, the minimum will start recording with the first reading.  Usually the user 
will reset the minimum once the motor is up to speed.  When slowing to a stop, the minimum will naturally tend to zero, but 
the maximum will be retained. 

Содержание ACT-3X

Страница 1: ...Totalizer Ratemeter User Manual and Reference Guide MONARCH INSTRUMENT 15 Columbia Drive Amherst NH 03031 USA Phone 603 883 3390 Fax 603 886 3300 E mail support monarchinstrument com Website www mona...

Страница 2: ...e personal injury or death may occur as a result 7 This instrument may not be safe for use in certain hazardous environments and serious personal injury or death could occur as a result of improper us...

Страница 3: ...4 3 2 3 UP and DOWN BUTTONS 5 3 2 4 RECALL BUTTON 5 4 0 OPERATION 5 4 1 Modes of Operation Channel 1 5 4 1 1 RPM Mode 5 4 1 2 Frequency Mode 5 4 1 3 Scale Mode Ratemeter 5 4 1 4 Single Event Capture S...

Страница 4: ...5 9 11 5 10 11 5 11 12 5 12 12 6 0 SERIAL OUTPUT 12 6 1 Data from the Serial Interface 12 6 2 Serial Commands 12 6 2 1 Run Mode Commands 12 6 2 2 Control Commands 13 7 0 SPECIFICATIONS 14 8 0 OPTIONS...

Страница 5: ...xed equipment or permanently connected If permanently connected disconnection from the supply must be possible via a customer supplied switch or circuit breaker rated at 120V or 240V dependent on loca...

Страница 6: ...ve Hot wire to the terminal marked L and the Neutral Return wire to the terminal marked N NOTE The ground connection is not required as the unit is fully isolated from the mains If the unit is dc powe...

Страница 7: ...nput is also referred to as Channel 2 CH 2 and will accept a TTL input or any signal up to 12Vdc It has a weak pull up internally and can be used with a set of potential free contacts The AUX input is...

Страница 8: ...is another input pulse It is more useful at slow speeds as it appears to be on continuously at higher inputs It gives an indication that a valid input trigger signal is present 3 1 3 MAX and MIN LEDS...

Страница 9: ...1 2 Frequency Mode In the Frequency Mode the unit displays input pulses per second or more commonly Hertz Hz This is the most basic mode of operation The range of measurement in this mode is 0 0833 t...

Страница 10: ...nding on the sense programmed It acts as a gate preventing the input signal from updating the unit 4 2 3 Single Event Capture When programmed as Single Event Capture this input acts as the second inpu...

Страница 11: ...become de energized Thus in the event of a power failure the relays will drop out by default creating the equivalent of an alarm condition 4 5 Analog AO and Current IO Output The ACT 3X has options f...

Страница 12: ...or 14 640 RPM the internal update rate is the period of the input frequency Thus the response of the alarms etc can be seen to be a function of the input Above an input of 244 Hz the alarms respond wi...

Страница 13: ...d scale factor Press RECALL to exit up one level without making a change or press SET to save the change The edit buttons function as follows RESET changes the digit being edited blinking digit UP inc...

Страница 14: ...EGative or POSitive Press the SET button to select the new setting or the RECALL button to exit without saving the settings 5 3 Sets the decimal point on the displayed reading To enter this menu item...

Страница 15: ...a change or press SET to save the change 5 6 2 FULL SCALE Sets the Full Scale value for the Analog output Press the SET button and use the buttons to edit the value as per above Press RECALL to exit u...

Страница 16: ...ent occurs Other information is sent on demand and is covered in the following section The messages are sent as standard ASCII and all messages end with a carriage return CR There is no Line feed sent...

Страница 17: ...mand Category Argument Value eg CH_1 TYPE SCALE 60 0 sets the Scale Mode Scale factor to 60 0 Command Argument eg DECPT NONE sets the Decimal Point to none Command Category Argument Action CH_1 Channe...

Страница 18: ...100 times per second Standard Gate or up to 1000 Fast Gate Dependent on input frequency Input must be measurement rate Scale Mode Scaling Computation Programmable scaling 0 0001 to 99 999 Front panel...

Страница 19: ...preadsheet Software available for download at www monarchinstrument com ROLS W Remote Optical Laser Sensor with 8 foot cable ROS W Remote Optical Sensor with 8 foot cable ROS P 25 Remote Optical Senso...

Страница 20: ...ing the circumference of the shaft you are monitoring This could also be a speed wheel tire etc The circumference x diameter 3 14159 In order to scale we need to know what we want as opposed to what w...

Страница 21: ...il the display shows and then press the SET button The display will show the current scale factor value with the right most digit flashing The UP and DOWN buttons change the flashing digit The RESET b...

Страница 22: ...an error in the placement of the sensors The tape edges won t be exactly 1 inch apart Assuming the edges were really 1 01 inches apart there would be 1 error So at 130 MPH your reading would be 128 7...

Страница 23: ...hat the device is set up for DHCP by default so it will get an IP address from your local server Once the search is complete the window will be populated as shown next The current device setting is sh...

Страница 24: ...ons to set the required value Press RECALL to exit up one level without making a change or press SET to make the change The edit buttons function as follows RESET changes the digit being edited blinki...

Отзывы: