Non-Latched Alarms
Alarm condition present when the alarm is acknowledged.
ALM beacon on continuously.
The alarm message(s) will continue to scroll.
This state will continue for as long s the alarm condition remains. When the alarm condition
disappears all indication also disappears.
If the alarm condition disappears before it is acknowledged the alarm reset immediately
.
5.5
Automatic Air Purge Operation (Start-Up)
All systems with this controller are equipped with our auto-air purge function, it is factory set for
five (5) minutes. When the system is started, the controller will operate a timer for five (5)
minutes. The controller should be set at the minimum temperature, and the scrolling text will read
“Auto Air Purge.” OP4 and Run will illuminate on the controller. The system should automatically be
purged of air at the end of the five (5) minute timer. If pressure gauges are still erratic or air
appears to still be present, refer to Section 5.6 for restarting the automatic air purge timer.
Adjusting Auto Air Purge Timer (Factory Default Set for 5 Minutes)
Press scroll button, toggling until you see the parameter DWELL.
Using the arrow keys, change to desired setting
The DWELL parameter relates to time in minutes. (The amount of time it will take to purge
your process loop will be affected by the size of the loop and the backpressure on your
drain.)
Wait for the display to flash.
Press Page button.
Unit will return back to the normal user screen.
Symbols:
Refer to Section 3.1 for Initial Starting Procedure for air bleed and air separator devices
on process.