Seal Replacement/Maintenance
Warning: Make certain that the system is disconnected from the power
source in compliance with all local and national codes before attempting
to service or remove any components. Never run the pump when dry.
Maintenance:
Inspection: Pump should be periodically checked for proper operation. If the system has changed
or if the pump is operating noisily or erratically, then the pump should be removed and examined.
It should be repaired and parts replaced as necessary.
Cleaning: Remove oil, dust, dirt, water, chemicals from exterior of pump and motor. Blow out
interior of open motors with clean compressed air at low pressure. Regularly drain moisture from
TEFC motors.
Draining: If the pump is located in an area subject to freezing temperatures, the pump must be
drained when not in operation or add sufficient antifreeze.
Seal Replacement:
Disassembly:
Turn off power.
Close suction and discharge valves (if equipped).
Drain pump.
Remove bolts holding base to foundation.
Remove casing bolts.
Remove motor and rotating element from casing, leaving casing and piping undisturbed, if
possible. If not, then remove the whole assembly.
Insert a screwdriver in one of the impeller waterway passages and back off the impeller nut.
Remove impeller from shaft, being careful not to lose the impeller key, spring and seal
retainer. If impeller is difficult to remove, it may be necessary to use a bearing puller to
remove.
Pry off rotating member of mechanical seal from motor shaft by using two (2) screwdrivers.
Remove bolts holding adapter to motor and take off adapter.
Place adapter on a flat surface with case rabbet facing down, and push out stationary part
of mechanical seal.
Inspect the shaft sleeve, shaft O-ring, and flinger. If damaged or worn remove and replace
with a new one.