Installation
21
02/09 AWB2723-1613en
EU5E-SWD-4D2R
X
Connect the sensors to the corresponding input I0 to I3.
X
Connect the reference potential 0 V DC to connection 0 V.
X
Wire the first relay output to Q1 and the second to Q2.
The connection terminals are suitable for cables AWG22 to
AWG16 and flexible conductors with a cross section of 0.5
to 1.5 mm
2
.
Connections/power supply
Figure 9:
Wiring of the E-/A modules
h
Caution!
The relays Q1 and Q2 can be subjected to a rated
operational current of up to AC-15, 3 A at 250 V. They
must be protected with a 4 A fuse.
EU5E-SWD-8DX
EU5E-SWD-4D4D
EU5E-SWD-4D2R
0 V
24 V DC
0 V
0 V
0 V
0 V
24 V
0 V
L
N
4 A
4 A