I/O Modules EU5E-SWD-8DX
EU5E-SWD-4D4D EU5E-SWD-
4D2R
22
02/09 AWB2723-1613en
Terminal capacity
• fine wire, cross-section 0.25 mm² to 1.5 mm², with ferrule
(minimum length 8 mm.)
• Solid: 0.14 mm² to 1.5 mm²
Commissioning
The automatic addressing of all slaves in the SmartWire-
Darwin network is performed via the gateway (actuation of
the configuration pushbutton on the gateway) during initial
operation. During the addressing process the SmartWire-
Darwin diagnostics LED flashes. Once the addressing process
is completed, the LED indicates a green continuous light.
Exchange of Modules
After replacement of the modules and connection of the
voltage the configuration button must be pressed. The new
module is assigned an address by this means.
h
Caution!
Replacement of the SmartWire-Darwin input/output
modules is not permitted until the entire SmartWire-
Darwin system has been switched off.
h
Caution!
The order of the SmartWire-Darwin units must not be
altered.