Control Circuit Devices M22-
SWD…
66
02/09 AWB2723-1613en
Table 7:
Configurations of the M22-A adapter
Function element
Configuration of the M22-A adapter (front fixing)
(viewed from the rear while equipping the adapter)
Marking on adapter
1/4
3/6
2/5
M22-SWD-K11
O
X
1)
O
2)
M22-SWD-LED
O
X
O
M22-SWD-K11LED
O
X
O
M22-SWD-K22
O
X
X
M22-SWD-K22LED
O
X
X
1) X = occupied by SWD element
2) O = optional for an additional M22-K10/K01 element
h
The function elements obtain the energy for
communication electronics and driving the LED from the
SmartWire-Darwin network supply.
Please take into consideration the total current
consumption of your SmartWire network and, if necessary,
plan for an additional feeder module EU5C-SWD-PF2-1.
You will find information on the current consumption in
the appendix on page 103.
The software programme SWD-Assist also supports you in
doing this by automatically performing these calculations.