Control Circuit Devices M22-
SWD…
94
02/09 AWB2723-1613en
M22-SWD-KC22
The function element has one input byte at its disposal.
Inputs
Byte 0:
NO2
NC2
NO1
NC1
7
6
5
4
3
2
1
0
-
P
-
F
NO2
NC2
NO1
NC1
Bit
Designation
Meaning
0
NC1 = Normally Close
0: contact 1 actuated
1: contact 1 not actuated
1
NO1 = Normally Open
0: Contact 1 not actuated
1: contact 1 actuated
2
NC2 = Normally Close
0: contact 2 actuated
1: contact 2 not actuated
3
NO2 = Normally Open
0: contact 2 not actuated
1: contact 2 actuated
4
F = Failure
0: No diagnostic alarm
1: Diagnostics available
5
not used
-
6
P = Modules present
0: Module not available
1: Module available
7
not used
-