Engineering
63
02/09 AWB2723-1613en
Engineering
The SmartWire-Darwin front function elements are used
instead of the previous M22-K10-/K01 contact elements and
the corresponding M22 LED....indicator elements. The
previous elements for the control circuit function are used on
the front.
One SmartWire function element is used per M22-A adapter.
Mounting is always performed in the middle position.
Correspondingly more efficient function elements are used
for the combined functions of a luminous command device
or for the realization of a multi-step switch. An illuminated
pushbutton, which previously had to be realized as a
combination of several elements, can now be realized simply
by means of one combination element (LED ind
contact element = M22-SWD-K11LED).
M22-SWD-K11
This function element replaces the previous contact
elements M22-K10/K01. It provides a changeover contact by
means of which both a breaker and maker function can be
realized. The previously possible “piggy-back” combination
consisting of an M22-K01 and -K10 element can also be
replaced by a single M22-SWD-K11 element. The function
element is used in combination with M22 (pushbutton)
actuators.
M22-SWD-K22
This function element replaces multiple combinations of the
previous contact elements M22-K10/K01. It provides two
changeover contacts, by means of which control switches
can be operator controlled with up to three-position
indication.
h
Further M22-K10-/01 contact elements can be installed
here in the free location of the M22-A adapter.
A possible application is, for example, conventional
switching via an M22-K... contact element and the
reporting of this process to the PLC via the M22-SWD-K11
function element.