EU5C-SWD-PF1-1
9
02/09 AWB2723-1613en
Installation
The SmartWire-Darwin power module EU5C-SWD-PF1 is
envisaged for mounting on a top hat rail.
X
Mount the module on the top hat rail.
X
Connect the 24 V DC voltage to the terminals AUX on the
front of the module.
X
Connect the 8-pole SmartWire-Darwin cable to the SWD In
socket. The continuation to the next SmartWire-Darwin
module is from the SWD Out socket.
The terminals are suitable for cables AWG24 to AWG16 and
flexible conductors with a cross section of 0.5 to 1.5 mm
2
.
Figure 2:
Terminal capacity
• fine wire, cross-section 0.25 mm² to 1.5 mm², with the
ferrule (minimum length 8 mm)
• Solid: 0.14 mm² to 1.5 mm²
3
A
3
A
3
A
24 V DC
0 V
h
Information on the cable protection is provided on
page 14