3. Connect the multimeter between the copper
grounding bar and the metal portion of the
fireplace’s front panel as shown in Figures 20a
and 20b. Verify that the reading is 0 Ohms
(within 0.1 Ohms of the reference value
previously noted).
4. Likewise, connect the multimeter alternatively
between the copper grounding bar and the side
metal, rear metal, light-bar, and boiler metal
parts of the fireplace. Verify that the readings
are within 0.1 Ohms of the reference value for
each test.
If any of the reference readings are 0.2 Ohms or
greater, contact a factory representative before
completing the installation.
Figure 20b (Front Panel Metal)
Figure 20a (Ground Bar)