12
-
Corrects the starting time of next operation by
calculating the temperature difference.
(Example) Heating
Setting temperature
Room temperature
Operation starting time
Time
Setting time
15 min.
10 min.
5 min.
earlier
earlier
earlier
¡
If the difference (= Setting temperature – Room tempera-
ture) is 4ºC, the correction value is found to be +5 min-
utes from the table shown above so that the starting time
of next operation is determined as follows:
15 min. e 5 min. = 20 min. earlier
↑
↑
Current operation
Correction value
start time
(6)
Comfortable timer setting
If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode operation
is selected, the comfortable timer starts and determines the starting time of next operation based on the initial value of 15 minutes and the
relationship between the room temperature at the setting time (temperature of room temperature sensor) and the setting temperature.
(Max. 60 minutes)
Operation mode
Operation start time correction value (Min.)
3 < Room temp. – Setting temp.
1 < Room temp. – Setting temp.
≤
3
Room temp. – Setting temp.
≤
1
At cooling
+5
No change
–5
3 < Setting temp. – Room temp.
2 < Setting temp. – Room temp.
≤
3
Setting temp. – Room temp.
≤
2
At heating
+5
No change
–5
Notes (1) At 5 minutes before the timer ON time, operation starts regardless of the temperature of the room temperature sensor (Th1).
(2) This function does not operate when in the Dry or Auto Dry mode.
However, the operation in item (1) does operate in the Auto Dry mode.
(3) During the comfortable timer operation, both the RUN light and TIMER light illuminate and the TIMER light goes off after expiration of the timer, ON setting
time.
=
=
=
=
(7)
Outline of heating operation
(a)
Operation of major functional components in heating mode
(b)
Air flow selection
(i)
Speed of inverter changes within the range of selected air flow.
(ii)
When the defrosting, protection device, etc. is actuated, operation is performed in the corresponding mode.
(iii)
Outdoor unit blower operates in accordance with the inverter command speed.
Item
Indoor fan motor
ON
ON
OFF
Flaps
ON or OFF
ON or OFF
Stop position control
Display
Lights up
Lights up
Lights up or flashes
52C
ON
ON
OFF after stop mode
Outdoor fan motor
OFF
ON
OFF
4-way valve
Depending on the stop mode
ON
Depending on the stop mode
Electronic expansion valve
Depending on the EEV control
Solenoid valve
OFF
OFF
OFF
When the inverter
speed is 0rps
When the inverter speed
is other than 0rps
When the inverter speed is 0rps
due to an anomalous stop
Functional
components
Model
SRK13ZEV-S
Air flow selection
Inverter command speed
12~118rps
Air flow
Depends on inverter command speed.
Inverter command speed
12~118rps
Air flow
Depends on inverter command speed.
Inverter command speed
12~78rps
Air flow
Depends on inverter command speed.
Inverter command speed
12~38rps
Air flow
4th speed fixed
Auto
HI
MED
LO
Содержание SRK10CES
Страница 2: ...TECHNICAL MANUAL...
Страница 204: ...202 MEMO...
Страница 208: ...CRAE0171 10 11 12 13 20 21 24 22 23 25 17 18 16 14 15 19 7 8 6 5 1 9 2 4 3 HEAT EXCH CONTROL 206...
Страница 213: ...211...
Страница 214: ...CRAE0168 21 1 9 3 8 7 6 5 4 2 23 11 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 212...
Страница 218: ...CRAE0141 1 4 5 6 7 8 10 11 12 13 14 15 19 20 21 25 26 23 24 22 16 9 2 3 18 17 HEAT EXCH CONTROL 216...
Страница 222: ...CRAE0141 1 4 5 6 7 8 10 11 12 13 14 15 19 20 21 25 26 23 24 22 16 9 2 3 18 17 HEAT EXCH CONTROL 220...
Страница 227: ...225...
Страница 228: ...CRAE0166 21 1 9 3 8 7 6 5 4 23 11 2 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 226...
Страница 233: ...231...
Страница 234: ...CRAE0166 21 1 9 3 8 7 6 5 4 23 11 2 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 232...
Страница 236: ...CRBE0226 1 3 4 2 5 6 7 8 9 10 11 12 13 PANEL FAN ASSY 234...
Страница 240: ...05 0 CRBE0207 2 12 6 1 7 14 3 24 16 19 4 9 10 5 11 11 13 15 8 18 17 20 23 21 22 PANEL FAN ASSY 238...
Страница 244: ...CRBE0228 9 15 7 8 1 2 4 5 6 12 13 14 10 11 3 PANEL FAN ASSY 242...
Страница 246: ...CRBE0190 1 2 4 3 5 6 7 8 13 10 14 15 12 11 9 GAS LIQ 18 19 20 17 21 16 CONTROL ASSY HEAT EXCH CONTROL 244...
Страница 248: ...CRBE0227 11 15 16 1 2 3 5 6 7 8 9 12 13 14 4 10 PANEL FAN ASSY 246...
Страница 250: ...CRBE0191 1 3 4 5 2 6 7 8 10 13 9 12 11 15 14 LIQ GAS CONTROL ASSY 17 18 16 HEAT EXCH CONTROL 248...
Страница 252: ...CRBE0221 12 16 17 1 2 3 5 6 7 8 9 10 13 16 14 15 4 11 PANEL FAN ASSY 250...
Страница 256: ...05 0 CRBE0224 2 1 5 16 3 9 11 12 4 7 8 6 6 17 17 10 13 15 14 PANEL FAN ASSY 254...
Страница 260: ...2005 ROOM AIR CONDITIONING TECHNICAL HANDBOOK...