138
-
(5) Comfortable timer setting
If the timer is set at ON when the operation select switch is set at the cooling, or the cooling in auto mode operation is selected, the
comfortable timer starts and determines the starting time of next operation based on the initial value of 15 minutes and the relationship
between the room temperature at the setting time (temperature of room temperature sensor) and the setting temperature. (Max. 60
minutes)
Operation mode
Operation start time correction value (Min.)
3 < Room temp. – Setting temp.
1 < Room temp. – Setting temp. =
< 3
Room temp. – Setting temp. =
< 1
At cooling
+5
No change
–5
Notes (1) At 5 minutes before the timer ON time, operation starts regardless of the temperature of the room temperature sensor (Th1).
(2) This function does not operate when in the Dry or Auto Dry and FAN mode.
However, the operation in item (1) does operate in the Auto Dry and FAN mode.
(3) During the pleasant reservation operation, both the run light and timer light illuminate and the timer light goes off after expiration of the timer, ON setting time.
(4) Flap control
Control the flap by AIRFLOW button on the wireless remote control.
(a)
Air scroll
The flap will be automatically set to the angle of air flow best to operation.
(i)
Starting time of operation
(ii)
When not operating
The flap returns to the position of air flow directly below, when operation has stopped.
(b)
Memory flap
While the flap is operating if the AIRFLOW button is pushed once, it stops swinging at an angle.
As this angle is memorized in the microcomputer, the flap will be automatically set to the angle when next operation is
started.
¡
Recommendable stopping angle of the flap
(c)
Swing flap
Flap moves in upward and downward directions continuously.
Horizontal
blowing
COOL•DRY
Corrects the starting time of next operation by
calculating the temperature difference.
(Example) Cooling
Room temperature
Setting temperature
Operation starting time
Time
Setting time
15 min.
10 min.
5 min.
earlier
earlier
earlier
¡
If the difference (= Room temperature – Setting tempera-
ture) is 4ºC, the correction value is found to be +5 min-
utes from the table shown above so that the starting time
of next operation is determined as follows:
15 min. e 5 min. = 20 min. earlier
↑
↑
Current operation
Correction value
start time
s
During cooling and
t
dry operation
Thick line : Rapid movement
Thin line : Slow movement
Stops for approximately
5 seconds in the
horizontal position.
Содержание SRK10CES
Страница 2: ...TECHNICAL MANUAL...
Страница 204: ...202 MEMO...
Страница 208: ...CRAE0171 10 11 12 13 20 21 24 22 23 25 17 18 16 14 15 19 7 8 6 5 1 9 2 4 3 HEAT EXCH CONTROL 206...
Страница 213: ...211...
Страница 214: ...CRAE0168 21 1 9 3 8 7 6 5 4 2 23 11 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 212...
Страница 218: ...CRAE0141 1 4 5 6 7 8 10 11 12 13 14 15 19 20 21 25 26 23 24 22 16 9 2 3 18 17 HEAT EXCH CONTROL 216...
Страница 222: ...CRAE0141 1 4 5 6 7 8 10 11 12 13 14 15 19 20 21 25 26 23 24 22 16 9 2 3 18 17 HEAT EXCH CONTROL 220...
Страница 227: ...225...
Страница 228: ...CRAE0166 21 1 9 3 8 7 6 5 4 23 11 2 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 226...
Страница 233: ...231...
Страница 234: ...CRAE0166 21 1 9 3 8 7 6 5 4 23 11 2 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 232...
Страница 236: ...CRBE0226 1 3 4 2 5 6 7 8 9 10 11 12 13 PANEL FAN ASSY 234...
Страница 240: ...05 0 CRBE0207 2 12 6 1 7 14 3 24 16 19 4 9 10 5 11 11 13 15 8 18 17 20 23 21 22 PANEL FAN ASSY 238...
Страница 244: ...CRBE0228 9 15 7 8 1 2 4 5 6 12 13 14 10 11 3 PANEL FAN ASSY 242...
Страница 246: ...CRBE0190 1 2 4 3 5 6 7 8 13 10 14 15 12 11 9 GAS LIQ 18 19 20 17 21 16 CONTROL ASSY HEAT EXCH CONTROL 244...
Страница 248: ...CRBE0227 11 15 16 1 2 3 5 6 7 8 9 12 13 14 4 10 PANEL FAN ASSY 246...
Страница 250: ...CRBE0191 1 3 4 5 2 6 7 8 10 13 9 12 11 15 14 LIQ GAS CONTROL ASSY 17 18 16 HEAT EXCH CONTROL 248...
Страница 252: ...CRBE0221 12 16 17 1 2 3 5 6 7 8 9 10 13 16 14 15 4 11 PANEL FAN ASSY 250...
Страница 256: ...05 0 CRBE0224 2 1 5 16 3 9 11 12 4 7 8 6 6 17 17 10 13 15 14 PANEL FAN ASSY 254...
Страница 260: ...2005 ROOM AIR CONDITIONING TECHNICAL HANDBOOK...