148
-
¡
Always use a Torque wrench and back up spanner to tighten the flare nut.
(c)
Air purge
(i)
Tighten all flare nuts in the pipings both indoor and outside will so as not to cause leak.
(ii)
Connect service valve, charge hose, manifold valve and vacuum pump as is illustrated below.
(iii) Open manifold valve handle Lo to its full width, and perform vacuum or evacuation.
Continue the vacuum or evacuation operation for 15 minutes or more and check to see that the vacuum gauge reads – 0.1 MPa
(– 76 cmHg).
(iv) After completing vacuum operation, fully open service valve (Both gas and liquid sides) with hexagon headed wrench.
(v)
Check for possible leakage of gas in the connection parts of both indoor and outdoor.
(b)
Connection of refrigerant piping
Indoor unit side
¡
Connect firmly gas and liquid side
pipings by Torque wrench.
Outdoor unit side
¡
Connect firmly gas and liquid side
pipings by Torque wrench.
¡
Specified torquing value:
Liquid side (ø6.35) : 15.7~19.6N·m (1.6~2.0kgf·m)
Gas side (ø9.52)
: 29.4~39.2N·m (3.0~4.0kgf·m)
(ø12.7)
: 39.2~49.0N·m (4.0~5.0kgf·m)
¡
Use one more spanner to fix the valve.
Spanner
(for fixing
the piping)
Torque
wrench
¡
Specified torquing value:
Liquid side (ø6.35) : 15.7~19.6N·m (1.6~2.0kgf·m)
Gas side (ø9.52)
: 29.4~39.2N·m (3.0~4.0kgf·m)
(ø12.7)
: 39.2~49.0N·m (4.0~5.0kgf·m)
Manifold
Valve
-76 cm Hg
Handle Lo
(pressure)
Charge hose
Stop valve
(Two-way valve)
Service port
Stop valve
(Three-way
valve)
Compound
(Gauge)
Pressure
gauge
Handle Hi
(pressure)
Charge hose
Vacuum pump
♦
Additional refrigerant charge
When refrigerant piping exceeds 7.5m conduct additional refrigerant charge after refrigerant sweeping.
7.5m over 10m:Additional charge amount per meter = 10g/m
10m over 15m:Additional charge amount per meter=30g/m
[Example]
How much amount of additional charge for 15m piping?
(10 – 7.5)m
×
10g/m+(15-10)m
×30
g/m=175g
175g for additional charge
¡
All models
(d)
Insulation of connecting portion
(i)
Cover the connecting portion of the refrigerant piping with the pipe cover and seal them.
If neglecting to do so, moisture occurs on the piping and water will drip out.
Vinyl tape
To cover the connecting portion with
insulation material materials, cut upper portion
and then seal it with insulation materials.
Содержание SRK10CES
Страница 2: ...TECHNICAL MANUAL...
Страница 204: ...202 MEMO...
Страница 208: ...CRAE0171 10 11 12 13 20 21 24 22 23 25 17 18 16 14 15 19 7 8 6 5 1 9 2 4 3 HEAT EXCH CONTROL 206...
Страница 213: ...211...
Страница 214: ...CRAE0168 21 1 9 3 8 7 6 5 4 2 23 11 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 212...
Страница 218: ...CRAE0141 1 4 5 6 7 8 10 11 12 13 14 15 19 20 21 25 26 23 24 22 16 9 2 3 18 17 HEAT EXCH CONTROL 216...
Страница 222: ...CRAE0141 1 4 5 6 7 8 10 11 12 13 14 15 19 20 21 25 26 23 24 22 16 9 2 3 18 17 HEAT EXCH CONTROL 220...
Страница 227: ...225...
Страница 228: ...CRAE0166 21 1 9 3 8 7 6 5 4 23 11 2 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 226...
Страница 233: ...231...
Страница 234: ...CRAE0166 21 1 9 3 8 7 6 5 4 23 11 2 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 232...
Страница 236: ...CRBE0226 1 3 4 2 5 6 7 8 9 10 11 12 13 PANEL FAN ASSY 234...
Страница 240: ...05 0 CRBE0207 2 12 6 1 7 14 3 24 16 19 4 9 10 5 11 11 13 15 8 18 17 20 23 21 22 PANEL FAN ASSY 238...
Страница 244: ...CRBE0228 9 15 7 8 1 2 4 5 6 12 13 14 10 11 3 PANEL FAN ASSY 242...
Страница 246: ...CRBE0190 1 2 4 3 5 6 7 8 13 10 14 15 12 11 9 GAS LIQ 18 19 20 17 21 16 CONTROL ASSY HEAT EXCH CONTROL 244...
Страница 248: ...CRBE0227 11 15 16 1 2 3 5 6 7 8 9 12 13 14 4 10 PANEL FAN ASSY 246...
Страница 250: ...CRBE0191 1 3 4 5 2 6 7 8 10 13 9 12 11 15 14 LIQ GAS CONTROL ASSY 17 18 16 HEAT EXCH CONTROL 248...
Страница 252: ...CRBE0221 12 16 17 1 2 3 5 6 7 8 9 10 13 16 14 15 4 11 PANEL FAN ASSY 250...
Страница 256: ...05 0 CRBE0224 2 1 5 16 3 9 11 12 4 7 8 6 6 17 17 10 13 15 14 PANEL FAN ASSY 254...
Страница 260: ...2005 ROOM AIR CONDITIONING TECHNICAL HANDBOOK...