Checking the indoor electrical equipment
(i)
Indoor unit circuit board check procedure
1) Press the unit’s ON/OFF button for 5 seconds or longer (a beep which indicates receiving will be emitted). Then check
the following items.
1
The indoor unit’s fan motor runs.
2
The run light lights up.
2) There should be voltage (AC 220 V) between terminals
1
and
2
on the terminal block.
With the analog tester set in the DC 30 V range, if the voltage at
2
(+) and
3
(-) is measured, the needle oscillates at
about 12V.
3) It is possible to run and stop the unit using the remote control.
If operation is as described above, the indoor unit’s board is normal.
Note (1) Check the voltage on the terminal block.
¡
Power supply : Between
1
-
2
(AC 220V)
¡
Signal : Between
2
-
3
(Changing between DC 0-Approx. 12V)
(ii)
Indoor unit fan motor check procedure
This is a diagnostic procedure for determining if the indoor unit’s fan motor or the circuit board is broken down.
1) Indoor unit printed circuit board output check
a) Turn off the power.
b) Remove the front panel, then disconnect the fan motor lead wire connector.
c) Turn on the power. If the unit operates when the ON/OFF button is pressed, if trouble is detected after the voltages in
the following figure are output for approximately 30 seconds, it means that the circuit board is normal and the fan
motor is broken down.
If the voltages in the following figure are not output at connector pins No.
1
,
4
and
5
, the indoor unit’s circuit
board has failed and the fan motor is normal.
(ii) DC Fan motor resistance check
Notes (1) Remove the fan motor and measure it without power connected to it.
Notes
(2) If the measured value is below the value when the motor is normal, it means
that the fan motor is faulty.
Measuring Point
Resistance when Normal
1
–
3
(Red – Black)
25 M
Ω
or higher
4
–
3
(White – Black)
30 k
Ω
or higher
1
2
3
4
5
6
1
2
3
4
5
6
FM
I
DC15V
Indoor unit
circuit board
DC 308V
DC several V
(4~6 V)
CNU
(–)
GND
Blue
Y
ello
w
White
Blac
k
Red
Содержание SRK10CES
Страница 2: ...TECHNICAL MANUAL...
Страница 204: ...202 MEMO...
Страница 208: ...CRAE0171 10 11 12 13 20 21 24 22 23 25 17 18 16 14 15 19 7 8 6 5 1 9 2 4 3 HEAT EXCH CONTROL 206...
Страница 213: ...211...
Страница 214: ...CRAE0168 21 1 9 3 8 7 6 5 4 2 23 11 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 212...
Страница 218: ...CRAE0141 1 4 5 6 7 8 10 11 12 13 14 15 19 20 21 25 26 23 24 22 16 9 2 3 18 17 HEAT EXCH CONTROL 216...
Страница 222: ...CRAE0141 1 4 5 6 7 8 10 11 12 13 14 15 19 20 21 25 26 23 24 22 16 9 2 3 18 17 HEAT EXCH CONTROL 220...
Страница 227: ...225...
Страница 228: ...CRAE0166 21 1 9 3 8 7 6 5 4 23 11 2 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 226...
Страница 233: ...231...
Страница 234: ...CRAE0166 21 1 9 3 8 7 6 5 4 23 11 2 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 232...
Страница 236: ...CRBE0226 1 3 4 2 5 6 7 8 9 10 11 12 13 PANEL FAN ASSY 234...
Страница 240: ...05 0 CRBE0207 2 12 6 1 7 14 3 24 16 19 4 9 10 5 11 11 13 15 8 18 17 20 23 21 22 PANEL FAN ASSY 238...
Страница 244: ...CRBE0228 9 15 7 8 1 2 4 5 6 12 13 14 10 11 3 PANEL FAN ASSY 242...
Страница 246: ...CRBE0190 1 2 4 3 5 6 7 8 13 10 14 15 12 11 9 GAS LIQ 18 19 20 17 21 16 CONTROL ASSY HEAT EXCH CONTROL 244...
Страница 248: ...CRBE0227 11 15 16 1 2 3 5 6 7 8 9 12 13 14 4 10 PANEL FAN ASSY 246...
Страница 250: ...CRBE0191 1 3 4 5 2 6 7 8 10 13 9 12 11 15 14 LIQ GAS CONTROL ASSY 17 18 16 HEAT EXCH CONTROL 248...
Страница 252: ...CRBE0221 12 16 17 1 2 3 5 6 7 8 9 10 13 16 14 15 4 11 PANEL FAN ASSY 250...
Страница 256: ...05 0 CRBE0224 2 1 5 16 3 9 11 12 4 7 8 6 6 17 17 10 13 15 14 PANEL FAN ASSY 254...
Страница 260: ...2005 ROOM AIR CONDITIONING TECHNICAL HANDBOOK...