21
-
(d)
Prevention of continuous low speed operation:
For oil return to compressor
(i)
Operating condition:
When command speed of less than 26 rps continues for 60 minutes
(ii)
Detail of operation:
The unit is operated at command speed of 30 rps forcibly for 15 seconds. (The indoor and outdoor
fans are not changed.)
Note (1) When the command of exceeding 30 rps is directed during 30 rps forced operation, the unit follows it.
(e)
Compressor protection start
(i)
When the indoor unit calculated speed is 64 rps or over at operation start, the unit is operated with 64 rps for 1 minute and 45
seconds.
(ii)
After (i) above, if the decision speed is 96 rps or higher, it runs for 5 minutes at 96 rps, then changes to the decision speed.
(iii)
At thermo operation (OFF
→
ON) this control is not executed.
(iv)
The indoor unit fan corresponds to the command speed of each operation mode.
Note (1) When the calculated speed is less than 64 rps, the unit is started with low load starting described in article (e).
(f)
Low load starting
(i)
When the unit is started with calculated speed of less than 30 rps, it is operated with 30 rps for 60 seconds, then the operation
is moved to the command speed.
(ii)
The indoor fan corresponds to the operation mode.
Cooling:
Speed corresponding to the command speed of air flow switching
Dehumidification:
Speed decided in the operation region
Heating:
The lower one between the speed corresponding to the command speed and the hot keep speed
(g)
Inching prevention
When the compressor goes into the thermo operation within 3 minutes since operation start or becomes various dehumidifying
operations, the operation is continued with the command speed of 12 rps forcibly.
(h)
Current safe
(i)
Purpose:
Current is controlled not to exceed the upper limit of the setting operation current.
(ii)
Detail of operation:
Input current to the converter is monitored with the current sensor fixed on the printed circuit board of
the outdoor unit and, if the operation current value reaches the limiting current value, the inverter speed is reduced.
If the mechanism is actuated when the speed of outdoor unit is less than 30 rps, the compressor is stopped immediately.
Operation starts again after a delay time of 3 minutes.
(i)
Current cut
(i)
Purpose:
Inverter is protected from overcurrent.
(ii)
Detail of operation:
Output current from the converter is monitored with a shunt resistor and, if the current exceeds the
setting value, the compressor is stopped immediately. Operation starts again after a delay time of 3 minutes.
(j)
Heating overload protective control
(i)
Operating conditions :
When the unit is operating with the outdoor unit speed other than 0 rps or when the outdoor air
temperature (detected by Th5) rose beyond 17ºC for 2 minutes continuously.
(ii)
Detail of operation
1)
Indoor fan speed is raised forcibly by 1 step. However, when the air flow is LO, the fan speed is not raised by 1 step.
2)
Taking the upper limit of control speed range at 60 rps, if the output speed obtained with the fuzzy calculation exceeds the
upper limit, the upper limit value is maintained.
3)
The outdoor fan is set on 2nd speed.
4)
JET operation control does not raise the speed by 1 step
5)
The lower limit of control speed is set to 35 rps and even if the calculated result becomes lower than that after fuzzy
calculation, the speed is kept to 35 rps. However, when the thermo becomes OFF, the speed is reduced to 0 prs.
(iii) Reset condition:
When the outdoor air temperature drops below 16ºC.
Содержание SRK10CES
Страница 2: ...TECHNICAL MANUAL...
Страница 204: ...202 MEMO...
Страница 208: ...CRAE0171 10 11 12 13 20 21 24 22 23 25 17 18 16 14 15 19 7 8 6 5 1 9 2 4 3 HEAT EXCH CONTROL 206...
Страница 213: ...211...
Страница 214: ...CRAE0168 21 1 9 3 8 7 6 5 4 2 23 11 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 212...
Страница 218: ...CRAE0141 1 4 5 6 7 8 10 11 12 13 14 15 19 20 21 25 26 23 24 22 16 9 2 3 18 17 HEAT EXCH CONTROL 216...
Страница 222: ...CRAE0141 1 4 5 6 7 8 10 11 12 13 14 15 19 20 21 25 26 23 24 22 16 9 2 3 18 17 HEAT EXCH CONTROL 220...
Страница 227: ...225...
Страница 228: ...CRAE0166 21 1 9 3 8 7 6 5 4 23 11 2 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 226...
Страница 233: ...231...
Страница 234: ...CRAE0166 21 1 9 3 8 7 6 5 4 23 11 2 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 232...
Страница 236: ...CRBE0226 1 3 4 2 5 6 7 8 9 10 11 12 13 PANEL FAN ASSY 234...
Страница 240: ...05 0 CRBE0207 2 12 6 1 7 14 3 24 16 19 4 9 10 5 11 11 13 15 8 18 17 20 23 21 22 PANEL FAN ASSY 238...
Страница 244: ...CRBE0228 9 15 7 8 1 2 4 5 6 12 13 14 10 11 3 PANEL FAN ASSY 242...
Страница 246: ...CRBE0190 1 2 4 3 5 6 7 8 13 10 14 15 12 11 9 GAS LIQ 18 19 20 17 21 16 CONTROL ASSY HEAT EXCH CONTROL 244...
Страница 248: ...CRBE0227 11 15 16 1 2 3 5 6 7 8 9 12 13 14 4 10 PANEL FAN ASSY 246...
Страница 250: ...CRBE0191 1 3 4 5 2 6 7 8 10 13 9 12 11 15 14 LIQ GAS CONTROL ASSY 17 18 16 HEAT EXCH CONTROL 248...
Страница 252: ...CRBE0221 12 16 17 1 2 3 5 6 7 8 9 10 13 16 14 15 4 11 PANEL FAN ASSY 250...
Страница 256: ...05 0 CRBE0224 2 1 5 16 3 9 11 12 4 7 8 6 6 17 17 10 13 15 14 PANEL FAN ASSY 254...
Страница 260: ...2005 ROOM AIR CONDITIONING TECHNICAL HANDBOOK...