26
-
(1)
Selection of location for installation
(a)
Indoor unit
(i)
Where there is no obstructions to the air flow and where the cooled
air can be evenly distributed.
(ii)
A solid place where the unit or the wall will not vibrate.
(iii) A place where there will be enough space for servicing. (Where
space mentioned below can be secured)
(iv) Where wiring and the piping work will be easy to conduct.
(v)
The place where receiving part is not exposed to the direct rays of
the sun or the strong rays of the street lighting.
(b)
Outdoor unit
(i)
A place where good air circulation can be obtained and where rain, snow or sunshine will not directly strike the unit.
(ii)
A place where discharged hot air or unit’s operating sound will not be a nuisance to the neighborhood.
(iii) A place where servicing space can be secured.
(iv) A place where vibration will not be enlarged.
Model
SRK13ZEV-S
Item
One way piping length (
R
)
25 m
Outdoor
unit is lower
15 m
Outdoor unit
is higher
15 m
r
h
Left
side
Right
side
5 cm
10 cm
1.5 cm
6.5 cm
Air inlet
Air inlet
Air
Outlet
100
100
600
No obstacles
(Service space
for electrical
parts)
Unit : mm
Notes (1) Blowing out port and suction port on the back side of the unit can be
installed at a distance of 10cm from walls.
In case the barrier is 1.2m or above in height, or is overhead, the
sufficient space between the unit and wall shall be secured.
(2) When the unit is installed, the space of the following dimension and
above shall be secured.
(v)
In heating operation, snow deposit on the heat-exchanger of outdoor unit must be
prevented for keeping the normal performance capacity.
1)
Snow-hood on outdoor unit as in drawing, will reduce the frequency of
defrost operation.
When installing the snow hood, take care so that the air outlet of the snow
hood will not face directly into the most windy direction.
2)
Design the base higher than possible snow deposit.
(c)
Limitations for one way piping length and vertical
height difference.
(
)
Vertical height
difference (h)
Snow hood
Height:
Must be over
the possible
snow deposit
height
Содержание SRK10CES
Страница 2: ...TECHNICAL MANUAL...
Страница 204: ...202 MEMO...
Страница 208: ...CRAE0171 10 11 12 13 20 21 24 22 23 25 17 18 16 14 15 19 7 8 6 5 1 9 2 4 3 HEAT EXCH CONTROL 206...
Страница 213: ...211...
Страница 214: ...CRAE0168 21 1 9 3 8 7 6 5 4 2 23 11 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 212...
Страница 218: ...CRAE0141 1 4 5 6 7 8 10 11 12 13 14 15 19 20 21 25 26 23 24 22 16 9 2 3 18 17 HEAT EXCH CONTROL 216...
Страница 222: ...CRAE0141 1 4 5 6 7 8 10 11 12 13 14 15 19 20 21 25 26 23 24 22 16 9 2 3 18 17 HEAT EXCH CONTROL 220...
Страница 227: ...225...
Страница 228: ...CRAE0166 21 1 9 3 8 7 6 5 4 23 11 2 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 226...
Страница 233: ...231...
Страница 234: ...CRAE0166 21 1 9 3 8 7 6 5 4 23 11 2 10 13 17 12 15 14 16 18 19 20 22 24 25 26 27 29 28 HEAT EXCH CONTROL 232...
Страница 236: ...CRBE0226 1 3 4 2 5 6 7 8 9 10 11 12 13 PANEL FAN ASSY 234...
Страница 240: ...05 0 CRBE0207 2 12 6 1 7 14 3 24 16 19 4 9 10 5 11 11 13 15 8 18 17 20 23 21 22 PANEL FAN ASSY 238...
Страница 244: ...CRBE0228 9 15 7 8 1 2 4 5 6 12 13 14 10 11 3 PANEL FAN ASSY 242...
Страница 246: ...CRBE0190 1 2 4 3 5 6 7 8 13 10 14 15 12 11 9 GAS LIQ 18 19 20 17 21 16 CONTROL ASSY HEAT EXCH CONTROL 244...
Страница 248: ...CRBE0227 11 15 16 1 2 3 5 6 7 8 9 12 13 14 4 10 PANEL FAN ASSY 246...
Страница 250: ...CRBE0191 1 3 4 5 2 6 7 8 10 13 9 12 11 15 14 LIQ GAS CONTROL ASSY 17 18 16 HEAT EXCH CONTROL 248...
Страница 252: ...CRBE0221 12 16 17 1 2 3 5 6 7 8 9 10 13 16 14 15 4 11 PANEL FAN ASSY 250...
Страница 256: ...05 0 CRBE0224 2 1 5 16 3 9 11 12 4 7 8 6 6 17 17 10 13 15 14 PANEL FAN ASSY 254...
Страница 260: ...2005 ROOM AIR CONDITIONING TECHNICAL HANDBOOK...