5.1 Utility Package Functions
Table 5.1 shows a list of the utility package functions.
Table 5.1 Utility Package (GX Configurator-TI) Function List
Function Description
Reference
section
(1) Make the initial setting for the following items on each channel.
• Conversion Enable/Disable Setting
• Sampling/Averaging Processing Selection (Q64RD)
• Extended Averaging Processing Selection
• Time/Count Averaging Selection (Q64RD)
• Time/Count/Moving Average/Time Constant Setting
2
• Warning Output Enable/Disable Setting
• Setting Range (Q64RD)
• Setting Range 1 (Q64RD-G)
• Warning Output Lower Lower Limit Value
• Warning Output Lower Upper Limit Value
• Warning Output Upper Lower Limit Value
• Warning Output Upper Upper Limit Value
• Scaling Range Lower Limit Value
• Scaling Range Upper Limit Value
• Scaling Width Lower Limit Value
• Scaling Width Upper Limit Value
• Conversion setting for disconnection detection
• Conversion setting value for disconnection
detection
Initial
setting
1
(2) The data set in the initial setting are stored as parameters in the programmable controller CPU, and
automatically written into the Q64RD/Q64RD-G when the programmable controller CPU is changed into
the RUN status.
Section 5.4
(1) Make the refresh setting for the following items on each channel.
• Conversion Completion Flag
• CH Measured Temperature Value (16bit)
• Error Code
• Setting Range (Q64RD)
• Setting Range 1 (Q64RD-G)
• Setting Range 2 (Q64RD-G)
• Warning Output Flag
• Disconnection Detection Flag
• CH Scaling Value
• CH Measured Temperature Value (32bit)
Auto
refresh
1
(2) The data in the Q64RD/Q64RD-G buffer memory set in the auto refresh setting are read or written to set
devices automatically when the END instruction of the programmable controller CPU is executed.
Section 5.5
Monitors and tests the buffer memory and I/O signals for the Q64RD/Q64RD-G.
• Module Ready
• Operating Condition Setting Completion Signal
• Operating Condition Setting Request
• Offset/gain Setting Mode Status Flag
• Disconnection Detection Signal
• Warning Output Signal
• Conversion Completion Flag
• Error Flag
• Error Clear Request
• Averaging Processing Selecion
• Extended Averaging Processing Selection
(1) CH Monitor/Test
Monitor/test
• Conversion Enable/Disable Setting
• Sampling/Averaging Processing Selection (Q64RD)
• Extended Averaging Processing Selection
• Time/Count Averaging Selection (Q64RD)
• Time/Count/Moving Average/Time Constant Setting
• Conversion Completion Flag
• Measured Temperature Value (16bit)
• Measured Temperature Value (32bit)
• Error Code
• Setting Range (Q64RD)
• Setting Range - Wire Connection (Q64RD)
• Setting Range 1 (Q64RD-G)
• Setting Range 2 - Wire Connection (Q64RD-G)
• Warning Output Enable/Disable Setting
• Warning Output Flag Lower Limit Value
• Warning Output Flag Upper Limit Value
• Warning Output Lower Lower Limit Value
• Warning Output Lower Upper Limit Value
• Warning Output Upper Lower Limit Value
• Warning Output Upper Upper Limit Value
• Disconnection Detection Flag
• Scaling Value
• Scaling Range Lower Limit Value
• Scaling Range Upper Limit Value
• Scaling Width Lower Limit Value
• Scaling Width Upper Limit Value
• Conversion setting for disconnection
detection
3
• Conversion setting value for disconnection
detection
3
Section 5.6
5
Содержание q64rd
Страница 1: ......
Страница 2: ......
Страница 62: ...3 39 3 39 MELSEC Q 3 SPECIFICATIONS MEMO ...
Страница 92: ...5 17 5 17 MELSEC Q 5 UTILITY PACKAGE GX Configurator TI X Y Monitor Test 1 OMC refresh ...
Страница 98: ...5 23 5 23 MELSEC Q 5 UTILITY PACKAGE GX Configurator TI MEMO ...
Страница 175: ......
Страница 176: ......