3 - 14 3 - 14
MELSEC-Q
3 SPECIFICATIONS
(2) Output signals
Device No.
Signal name
Description
Y1
Y3
Y5
Y7
CH
Offset
Setting Request
(1) This signal is made valid in the offset/gain setting mode.
(2) This signal corrects the temperature conversion value to be an offset temperature
set value when it is on.
(3) When this signal turns on while the Gain Setting Request on the same channel is on
or they turn on simultaneously, an error will occur and the operation in (2) not
performed.
(4) For the on/off timing, refer to the field of the CH Offset/Gain Setting Status Signal
(X1 to 4).
Y2
Y4
Y6
Y8
CH
Gain Setting
Request
(1) This signal is made valid in the offset/gain setting mode.
(2) This signal corrects the temperature conversion value to be a gain temperature set
value when it is on.
(3) When this signal turns on while the Offset Setting Request on the same channel is
on or they turn on simultaneously, an error will occur and the operation in (2) not
performed.
(4) For the on/off timing, refer to the field of the CH Offset/Gain Setting Status Signal
(X1 to 4).
Y9
Operating
condition setting
request
(1) This signal is turned on when the "Conversion enable/disable setting", "CH
time/count/moving average/time constant setting", "Averaging processing selection",
"Warning output enable/disable setting", "CH scaling range upper/lower limit
value", "CH
scaling width upper/lower limit value", "CH
warning output
upper/lower limit value", "Conversion setting for disconnection detection" or
"
CH
Conversion setting value for disconnection detection
"
is made valid.
(2) When this signal turns on, the Disconnection Detection Signal (XC) and Warning
Output Signal (XD) turn off.
(3) For the on/off timing, refer to the field of the Operating Condition Setting Completion
Signal (X9).
[In offset/gain setting mode]
(1) This turns on when the value adjusted based on the offset/gain settings is stored in
the E
2
PROM.
(2) See the XA column for ON/OFF timing.
See Section 4.6 for offset/gain settings.
YA
User Range Write
Request
[In normal mode]
(1) This signal turns on when the user range is restored.
(2) Refer to the field of XA for the ON/OFF timing.
Refer to Chapter 7 for user range restoration.
YF
Error Clear
Request
(1) This signal is turned on when the Error Flag (XF) and Disconnection Detection
Signal (XC) are cleared.
However, the set value error of the intelligent function module switch setting cannot
be cleared. Correct the set value.
(2) For the on/off timing, refer to the field of the Error Flag (XF).
Содержание q64rd
Страница 1: ......
Страница 2: ......
Страница 62: ...3 39 3 39 MELSEC Q 3 SPECIFICATIONS MEMO ...
Страница 92: ...5 17 5 17 MELSEC Q 5 UTILITY PACKAGE GX Configurator TI X Y Monitor Test 1 OMC refresh ...
Страница 98: ...5 23 5 23 MELSEC Q 5 UTILITY PACKAGE GX Configurator TI MEMO ...
Страница 175: ......
Страница 176: ......