3 - 27 3 - 27
MELSEC-Q
3 SPECIFICATIONS
3.4.10 Setting range 1 (Q64RD-G) (Un\G20)
(1) The setting of "Measurement range setting" is stored.
(2) Use the intelligent function module switches of GX Developer to make setting of
"Measurement range setting".
Refer to Section 4.5 for details of the setting method.
b15 b14 b13 b12 b11 b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
CH4
CH3
CH2
CH1
b3
b2
b1
b0
Measurement
Mode
New JIS
(Pt100)
Set
Value
0
Old JIS
(JPt100)
1
4
2
Set value of measurement range setting
-200 to 850
-20 to 120
0 to 200
-180 to 600
3
5
-20 to 120
0 to 200
8
-60 to 180
Measurement
Range
Ni100
3.4.11 Setting range 2 (Q64RD-G) (Un\G21)
(1) The settings of "Offset/gain setting" and "Wiring type setting" are stored.
(2) Use the intelligent function module switches of GX Developer to make setting of
"Offset/gain setting" and "Wiring type setting".
Refer to Section 4.5 for details of the setting method.
b15 b14 b13 b12 b11 b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
CH4
CH3
CH2
CH1
b3
b2
b1
b0
Wiring Type Setting
3-wire type
4-wire type
Set Value
0
1
Set value of wiring type setting
Offset/Gain Setting
Factory default
User setting
Set Value
0
1
Set value of offset/gain setting
0
0
Содержание q64rd
Страница 1: ......
Страница 2: ......
Страница 62: ...3 39 3 39 MELSEC Q 3 SPECIFICATIONS MEMO ...
Страница 92: ...5 17 5 17 MELSEC Q 5 UTILITY PACKAGE GX Configurator TI X Y Monitor Test 1 OMC refresh ...
Страница 98: ...5 23 5 23 MELSEC Q 5 UTILITY PACKAGE GX Configurator TI MEMO ...
Страница 175: ......
Страница 176: ......