5 - 21 5 - 21
MELSEC-Q
5 UTILITY PACKAGE (GX Configurator-TI)
(c) Error handling
Confirm that the ERR. LED for the Q64RD is off. If the ERR. LED is lit, click
on Close , check the error code on the monitor screen, and then perform
the offset/gain settings again.
5.6.4 OMC (Online Module Change) refresh data
Perform the following steps to save/restore the user range.
(1) Switch to the OMC refresh data screen
Perform the operation in Section 5.6.1 to display the OMC refresh data screen.
(2) User range saving
(a) Change the Setting value field of OMC refresh data read request to
"Request", and click the Execute test button.
When read is completed, the values are displayed in the Current value fields
of 3/4-wire type CH Factory default offset/gain value/3/4-wire type CH
User range settings offset/gain value/3/4-wire type CH User range settings
offset/gain resistance value.
(b) Compare the values with those in the range reference table, and record
them if they are correct.
Refer to Section 7.4 for the range reference table.
(3) User range restoration
(a) Set the recorded values in the Setting value fields of 3/4-wire type CH
Factory default offset/gain value/3/4-wire type CH User range settings
offset/gain value/3/4-wire type CH User range settings offset/gain
resistance value.