8 - 2 8 - 2
MELSEC-Q
8 TROUBLESHOOTING
Error Code
(Decimal)
Description Remedy
6
The set warning output upper/lower limit value is outside the
measurable temperature range specified for the used
platinum temperature-measuring resistor.
indicates the channel number set incorrectly.
indicates any of the following statuses.
0: The lower lower limit value is lower than the
measurement range.
1: The upper upper limit value is higher than the
measurement range.
2: Lower lower limit value > lower upper limit value
3: Lower upper limit value > upper lower limit value
4: Upper lower limit value > upper upper limit value
Set a correct value at the buffer memory address 86 to 117
(Un\G86 to 117). (Refer to Section 3.4.19.)
POINT
•
If two or more errors have occurred, the code of the error found by the
Q64RD/Q64RD-G first is stored. The latter errors are not stored.
•
The error can be cleared by turning on the error clear request (YF).
•
The error is cleared at the time of mode switching.
8