7 - 4 7 - 4
MELSEC-Q
7 ONLINE MODULE CHANGE
7.3 Online Module Change Procedure
There are the following online module change procedures depending on whether the
user range setting has been made or not, whether the initial setting of GX Configurator-
AD has been made or not, and whether the other system exists or not.
Range setting
Initial setting
Other system
Reference section
Factory default
GX Configurator-TI
—
Section 7.3.1
Factory default
Sequence program
—
Section 7.3.2
User range setting
GX Configurator-TI Present
Section
7.3.3
User range setting
GX Configurator-TI Absent
Section
7.3.4
User range setting
Sequence program Present
Section
7.3.5
User range setting
Sequence program Absent
Section
7.3.6
7.3.1 When factory default is used and initial setting was made with GX Configurator-TI
(1) Conversion
disable
(a) Set Conversion enable/disable setting (buffer memory address 0: Un\G0)
for all channel conversion disable and turn the operating condition setting
request (Y9) from OFF to ON to stop conversion.
After confirming that conversion has stopped with the Conversion
Completion Flag (buffer memory address 10: Un\G10), turn off Operating
Condition Setting Request (Y9).