Error code
Title and display conditions
Possible Cause
Diagnosis and action
E0/E4
Main remote controller communication failure
(Reception error)
Error code E0 is displayed if main remote control-
ler does not receive any signal from the indoor
unit for ref. address "0" for 3 minutes.
Error code E4 is displayed if indoor unit does not
receive any data from the main remote control-
ler for 3 minutes or indoor unit does not receive
any signal from the main remote controller for 2
minutes.
1.
Contact failure with transmission cable
1.
Check connection cable for damage or
loose connections at the FTC and main
remote controller terminals.
2.
Wiring procedure not observed.
(Cable length/cable diameter/number
of indoor units/number of main remote
controllers)
2. Check main remote controller and FTC
common wiring max cable length 500 m.
Only use 2-core cable.
Only connect 1 main remote controller to 1
FTC indoor unit board.
3. Fault on the indoor unit FTC board
section controlling Ref. address "0"
3. to 5.
If the problem is not solved by the above
measures then:
Turn the power to the indoor unit OFF and
then ON.
Power to both the indoor unit and outdoor
units should be switched OFF then ON.
(This may require switching 1 or 2 breakers
depending if the unit is powered indepen
-
dently from the outdoor unit).
If the E4 code is still displayed the FTC and/
or the main remote controller circuit board
should be replaced.
4.
Fault with the main remote controller
circuit board
5. Electrical noise causes interference
with transmission/reception of data for
main remote controller.
E3/E5
Main remote controller communication failure
(Transmission error)
Error code E3 is displayed if the main remote
controller cannot find an empty transmission
path and thus fails to transmit for 6 seconds or
the data received by the main remote controller
is different to what was sent (by the main remote
controller) 30 consecutive times.
Error code E5 is displayed if the FTC cannot find
an empty transmission path for 3 minutes and
thus cannot transmit or the data sent by the FTC
is different to what was expected 30 consecutive
times.
1. 2 or more main remote controllers have
been connected to the FTC.
1. Only connect 1 main remote controller to 1
FTC indoor unit board.
2.
Fault with main remote controller
transmission/receiving circuit board
2. to 4.
Turn the power to the indoor unit OFF and
then ON.
Power to both the indoor unit and outdoor
units should be switched OFF then ON.
(This may require switching 1 or 2 breakers
depending if the unit is powered indepen
-
dently from the outdoor unit).
If the E3/E5 code is still displayed the FTC
and/or the main remote controller circuit
board should be replaced.
3.
Fault with the main remote controller
circuit board
4. Electrical noise causes interference
with transmission/reception of data for
main remote controller.
E6
Indoor/outdoor communication failure
(Reception error)
Error code E6 is displayed if after the power is
switched ON to the indoor unit, the FTC board
does not receive any signal or the signal received
is not complete for 6 minutes, or after a period of
operation the FTC board does not receive any
signal or the signal received is not complete for 3
minutes.
* Check the LED display on the outdoor unit
circuit board.
(Connect the A-control service tool, PAC-
SK52ST to test.) Refer to the outdoor unit
service manual for explanation of EA-EC
codes.
1.
Contact failure/short circuit/miswiring
1. Check the connections on the indoor and
outdoor units have not become loose and
that the connecting cable is not damaged.
2.
Fault with outdoor unit transmission/
receiving circuit board
2. to 4.
Turn the power to the indoor unit OFF and
then ON.
Power to both the indoor unit and outdoor
units should be switched OFF then ON.
(This may require switching 1 or 2 breakers
depending if the unit is powered indepen
-
dently from the outdoor unit).
If the E6 code is still displayed the FTC and/
or the outdoor unit circuit board should be
replaced.
3.
Fault with FTC transmission/receiving
circuit board
4. Electrical noise causes interference
with FTC-Outdoor unit transmission
cable.
E7
Indoor/outdoor communication failure
(Transmission error)
Error code E7 is displayed if despite the FTC
board sending signal "0", signal "1" is received
30 consecutive times.
1.
Fault with FTC transmission/receiving
circuit board
1. to 3.
Turn the power to the indoor unit OFF and
then ON.
Power to both the indoor unit and outdoor
units should be switched OFF then ON.
(This may require switching 1 or 2 breakers
depending if the unit is powered indepen
-
dently from the outdoor unit).
If the E7 code is still displayed the FTC
circuit board should be replaced.
2. Electrical noise causes interference
with power supply.
3. Electrical noise causes interference
with FTC-outdoor unit transmission ca
-
ble.
E1/E2
Main remote controller control board failure
Error code E1 displayed if main remote control-
ler cannot access it is non volatile (non power
dependent) memory.
Error code E2 is displayed when there is a fault
with the main remote controller's internal clock.
1.
Fault with the main remote controller
circuit board
1. Replace main remote controller circuit
board.