34
FIELD WIRING
7
Breaker abbreviation
Meaning
ECB1
Earth leakage circuit breaker for booster heater
ECB2
Earth leakage circuit breaker for immersion heater
TB1
Terminal block 1
Earth
leakage
circuit
breaker
*
1,
*
2
Wiring
circuit
breaker
or
Isolating
switch
Outdoor unit
Power
supply
~/N
230 V
50 Hz
Power
supply
~/N
230 V
50 Hz
Power
supply
~/N
230 V
50 Hz
Wiring
circuit
breaker or
Isolating
switch
Wiring
circuit
breaker or
Isolating
switch
To control
board
For
booster
heater
(Primary circuit)
For
Immersion
heater
(DHW tank)
Cylinder unit
Option 1: Cylinder unit powered via outdoor unit
<1 phase>
<Figure 7-1>
Electrical connections 1 phase
Description
Power supply
Capacity
Breaker
Wiring
Booster heater (Primary circuit)
~/N 230 V 50 Hz
2 kW
16 A
*
2
2.5 mm²
6 kW
32 A
*
2
6.0 mm²
Immersion heater (DHW tank)
~/N 230 V 50 Hz
3 kW
16 A
*
2
2.5 mm²
Wiring
Wiring
No.
×
siz
e
(m
m
²)
Cylinder unit - Outdoor unit
*
3
3 × 1.5 (polar)
Cylinder unit - Outdoor unit earth
*
3
1 × Min. 1.5
Circuit
rating
Cylinder unit - Outdoor unit S1 - S2
*
4
230 V AC
Cylinder unit - Outdoor unit S2 - S3
*
4
24 V DC
*
2
A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase conductors of the supply.
*
3
Maximum 45 m
If 2.5 mm² is used, maximum 50 m.
If 2.5 mm² is used and S3 is separated, maximum 80 m.
*
4
The values given in the table above are not always measured against the ground value.
Notes: 1. Wiring size must comply with the applicable local and national codes.
2. Indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
Indoor unit power supply cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60227 IEC 53)
3. Install an earth line longer than power cables.
4. Please keep enough output capacity of power supply for each heater. Insufficient power supply capacity might cause chattering.
*
1
If the installed earth leakage circuit
breaker does not have an over-current
protection function, install a breaker with
that function along the same power line.
Affix label A that is included with the manuals near each
wiring diagram for cylinder unit and outdoor units.
OCH570C