5.  Electrical work

5.3.  Types of control cables

1.  Wiring transmission cables

Types of transmission cable

Shielding wire CVVS or CPEVS

Cable diameter

More than 1.25 mm

(AWG16)

Length

Less than 200 m, 219 yard

2.  M-NET Remote control cables

Types of remote control cable

Shielding wire MVVS

Cable diameter

More than 0.5 (AWG20) to 1.25 mm

(AWG16)

Length

Add  any  portion  in  excess  of  10  m,  33  ft  to 

within  the  longest  allowable  transmission 

cable length 200 m, 219 yard.

3.  MA Remote control cables

Types of remote control cable

2-core cable (unshielded)

Cable diameter

0.3 (AWG22) to 1.25 mm

(AWG16)

Length

Less than 200 m, 219 yard

1

2

Fig. 5-3

3

5.4.  Connecting remote controller, indoor and outdoor 

transmission cables (Fig. 5-3)

•  Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire) The “S” on 

indoor unit TB5 is a shielding wire connection. For specifications about the con

-

necting cables, refer to the outdoor unit installation manual.

•  Install a remote controller following the manual supplied with the remote controller.

•  Connect the remote controller’s transmission cable within 10 m, 33 ft using a 0.75 

mm

2

 (AWG18) core cable. If the distance is more than 10 m, 33 ft, use a 1.25 mm

2

 

(AWG16) junction cable.

1

  MA Remote controller

•  Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Non-polarized 

2-wire)

•  DC 9 to 13 V between 1 and 2 (MA remote controller)

2

  M-NET Remote controller

•  Connect  the  “M1”  and  “M2”  on  indoor  unit TB5  to  a  M-NET  remote  controller. 

(Nonpolarized 2-wire)

•  DC 24 to 30 V between M1 and M2 (M-NET remote controller)

3

  Wireless remote controller (When installing wireless signal receiver)

•  Connect the wire of wireless signal receiver (9-pole cable) to CN90 of indoor con-

troller board.

•  When  more  than  two  units  are  run  under  group  control  using  wireless  remote 

controller, connect TB15 each with the same number.

•  To change Pair No. setting, refer to installation manual attached to wireless remote 

controller. (In the default setting of indoor unit and wireless remote controller, Pair 

No. is 0.)  

Terminal block for indoor transmission cable 

Terminal block for outdoor transmission cable (M1(A), M2(B),  (S))

Remote controller 

Wireless signal receiver 

E

 Wireless remote controller

Fig. 5-4

5.5.  Setting addresses (Fig. 5-4)

(Be sure to operate with the main power turned OFF.)

•  There are two types of rotary switch setting available: setting addresses 1 to 9 and 

over 10, and setting branch numbers.

1

 How to set addresses

  Example: If Address is “3”, remain SW12 (for over 10) at “0”, and match SW11 

(for 1 to 9) with “3”.

2

 How to set branch numbers SW14 (Series R2 only)

  Match the indoor unit’s refrigerant pipe with the BC controller’s end connection 

number.

  Remain other than series R2 at “0”.

•  The rotary switches are all set to “0” when shipped from the factory. These switches 

can be used to set unit addresses and branch numbers at will.

•  The determination of indoor unit addresses varies with the system at site. Set them 

referring to the Data Book.

Address board

5.6.  Sensing room temperature with the built-in sensor 

in a remote controller (Fig. 5-4)

If you want to sense room temperature with the built-in sensor in a remote controller, 

set  SW1-1  on  the  control  board  to  “ON”. The  setting  of  SW1-7  and  SW1-8  as 

necessary also makes it possible to adjust the air flow at a time when the heating 

thermometer is OFF.

Содержание City Multi Series PLFY-P08NCMU-E

Страница 1: ...avant d installer ce climatiseur pour viter tout accident et vous assurer d une utilisation correcte MANUAL DE INSTALACI N Para un uso seguro y correcto lea detalladamente este manual de instalaci n a...

Страница 2: ...ipping water When the room humidity exceeds 80 or when the drainpipe is clogged water may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing...

Страница 3: ...nstallation template top of the package and the gauge supplied as an accessory with the grille make an opening in the ceiling so that the main unit can be installed as shown in the diagram The method...

Страница 4: ...nto the suspension bolts in the order of the washers with insulation washers without insulation and nuts double Fit the washer with cushion so that the insulation faces downward In case of using upper...

Страница 5: ...at surface Copper pipe O D mm inch Flare dimensions A dimensions mm inch 6 35 1 4 8 7 9 1 11 32 23 64 9 52 3 8 12 8 13 2 1 2 33 64 12 7 1 2 16 2 16 6 41 64 21 32 15 88 5 8 19 3 19 7 49 64 25 32 19 05...

Страница 6: ...it B Insulating material C Band large D Drain port transparent E Insertion margin F Matching G Drain pipe O D 32 mm 1 1 4 inch PVC TUBE H Insulating material purchased locally I Transparent PVC pipe J...

Страница 7: ...6 2 4 Type 2 PEFY NMAU 38 1 6 Type 3 PEFY NMHSU 13 8 4 8 Others Other indoor unit 0 0 C Multiple of tripping current at tripping time 0 01s Please pick up C from the tripping characteristic of the br...

Страница 8: ...mote controller When installing wireless signal receiver Connect the wire of wireless signal receiver 9 pole cable to CN90 of indoor con troller board When more than two units are run under group cont...

Страница 9: ...ad the remote controller cord from the back of the controller B 2 To run the remote controller cord through the upper portion 3 For direct installation on the wall C Wall D Conduit E Lock nut F Bushin...

Страница 10: ...mp end 1 3 16 to 2 in B Cover of water supply inlet C About 1000 cc 1 4 gal D Water E Drain plug Fig 6 2 Fig 7 1 1 4 5 2 3 7 Installing the grille 7 1 Check the grille accessories Fig 7 1 The grille s...

Страница 11: ...er panel A Intake grille B Grille C Intake grille levers D Grille hook Fig 7 2 7 Installing the grille 7 3 Installing the grille Please pay attention because there is a restriction in the attachment p...

Страница 12: ...m on and drop from the ceiling or the unit could malfunction Fig 7 9 A Button B Vane motor C Up down vanes D Connector 7 3 4 Wire connection Fig 7 8 Be sure to connect the unit to the connector white...

Страница 13: ...13...

Страница 14: ...ttes d eau peuvent tomber de l appareil int rieur Ne pas installer l appareil int rieur dans un endroit o ces gouttes peuvent provoquer des dommages Lors de l installation de l appareil dans un h pita...

Страница 15: ...ma d installation dans le haut du colis et le gabarit fourni comme accessoire avec la grille pour cr er une ouverture dans le plafond de sorte pouvoir installer l appareil principal comme illustr sur...

Страница 16: ...sion dans l ordre rondelles avec isolant rondelles sans isolant et crous double Placer la rondelle avec isolant de telle sorte que la partie isolante soit tourn e vers le bas En cas d utilisation de r...

Страница 17: ...ique sur toute la surface d appui vas e Diam ext Tuyau en cuivre mm inch Dimensions vasement Dimensions A mm inch 6 35 1 4 8 7 9 1 11 32 23 64 9 52 3 8 12 8 13 2 1 2 33 64 12 7 1 2 16 2 16 6 41 64 21...

Страница 18: ...ati re isolante C Courroie grands D Port de drainage transparent E Marge d insertion F Correspondance G Tuyau de drainage Tuyau en PVC D E 32 mm 1 1 4 inch H Mati re isolante se procurer sur place I T...

Страница 19: ...2 4 Type 2 PEFY NMAU 38 1 6 Type 3 PEFY NMHSU 13 8 4 8 Autres Autre appareil int rieur 0 0 C Courants d ouverture l ouverture 0 01 s S lectionnez C partir des caract ristiques d ouverture du disjoncte...

Страница 20: ...eur de signaux sans fil Relier le fil du r cepteur de signaux sans fil c ble 9 p les au connecteur CN90 du bornier du contr leur int rieur Lorsque plus de deux appareils sont utilis s dans le cadre d...

Страница 21: ...ri re la t l com mande B 2 Pour faire passer le cordon de la t l comamnde travers la partie sup rieure 3 Pour l installer directement au mur C Mur D Conduit E Contre crou F Manchon G Bo te de commutat...

Страница 22: ...change 6 V rifier le bon fonctionnement du ventilateur de l appareil ext rieur 7 Arr ter l essai de fonctionnement en appuyant sur la touche ON OFF Marche Ar r t Arr t 8 Enregistrez un num ro de t l p...

Страница 23: ...ochet de la grille Fig 7 2 7 Installer la grille 7 3 Installer la grille Faire tr s attention aux restrictions concernant la position de fixation de la grille 7 3 1 Pr paratifs Fig 7 5 Installer les d...

Страница 24: ...ers le bas au del de la plage indiqu e De la condensation pourrait appara tre et provoquer l apparition de gouttes au plafond ou l appareil risquerait de mal fonctionner 7 5 Installation de la grille...

Страница 25: ...25...

Страница 26: ...idad interior en lugares donde el goteo pueda causar da os Si instala la unidad en un hospital o en un centro de comunicaciones re cuerde que la unidad produce ruidos e interferencias electr nicas Los...

Страница 27: ...n parte superior del paquete y el calibre sumi nistrado como un accesorio junto a la rejilla realice una apertura en el techo de forma que la unidad principal se pueda instalar tal y como se indica en...

Страница 28: ...dobles Coloque la arandela con el acolchado de forma que el aislamiento mire hacia abajo Si se utilizan arandelas superiores para colgar la unidad principal las arandelas inferiores con aislamiento y...

Страница 29: ...a superficie abocardada Tubo de cobre O D mm inch Dimensiones de abocinado dimensiones A mm inch 6 35 1 4 8 7 9 1 11 32 23 64 9 52 3 8 12 8 13 2 1 2 33 64 12 7 1 2 16 2 16 6 41 64 21 32 15 88 5 8 19 3...

Страница 30: ...ce VP25 tubo de PVC de 32 mm 1 1 4 inch para el tubo de drenaje y prevea una pendiente de descenso de 1 100 o m s Aseg rese de conectar las juntas de los tubos con un adhesivo de tipo polivinilo Obser...

Страница 31: ...er ser compatible con el circuito del inversor El interruptor de fuga a tierra deber combinarse mediante un conmutador local o un interruptor de cableado 2 Tome el F1 o el F2 m s grande como valor par...

Страница 32: ...de se ales inal mbricas cable de 9 polos a CN90 en el cuadro de control interior Si hay m s de dos unidades funcionando bajo el control de grupo utilizando el controlador remoto inal mbrico conecte ca...

Страница 33: ...o por detr s del control B 2 Para pasar el cable del control remoto por la parte de arriba 3 Para instalarla en la pared C Pared D Conducto E Tuerca de seguridad F Casquillo 2 Procedimientos de conexi...

Страница 34: ...locidad del aire Compruebe que cambia la velocidad del aire 6 Compruebe el funcionamiento del ventilador de la unidad exterior 7 Desactive la prueba de funcionamiento pulsando el bot n de activaci n d...

Страница 35: ...D Gancho de la rejilla Fig 7 2 7 Instalaci n de la rejilla 7 3 Instalaci n de la rejilla Preste especial atenci n debido a la restricci n existente en la colocaci n de la posici n de la rejilla 7 3 1...

Страница 36: ...ecificado Se podr a formar condensaci n y gotear desde el techo o podr a producrise un funcionamiento incorrecto de la unidad Fig 7 9 A Bot n B Motor de la paleta C Paletas de ascenso descenso D Conec...

Страница 37: ...37...

Страница 38: ...n this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment Printed in Thailand BH79D034H04 HEAD OFFICE...

Отзывы: