background image

10

2

 

Wiring examples

•  Controller name, symbol and allowable number of controllers.

Name

Symbol

Allowable number of controllers

Outdoor unit controller

OC

Indoor unit controller

IC

PUMY-P100

1 to 8 units per 1 OC

PUMY-P125

1 to 10 units per 1 OC

PUMY-P140

1 to 12 units per 1 OC

Remote controller

RC

(M-NET)

Maximum of 12 controllers 
for 1 OC

RC

MA

Maximum of 2 per group

6.3.  Wiring transmission cables

1

 

Types of control cables

1.  Wiring transmission cables
•  Types of transmission cables: Shielding wire CVVS or CPEVS or MVVS
•  Cable diameter: More than 1.25 mm

2

 

•  Maximum wiring length: Within 200 m

2.  M-NET Remote control cables

Kind of remote control cable

Sheathed 2-core cable (unshielded) CVV

Cable diameter 

0.3 to 1.25 mm

(0.75 to 1.25 mm

2

)*

Remarks 

When 10 m is exceeded, use cable with the 
same specifications as 1. Wiring transmission 
cables.

* Connected with simple remote controller.

Example of a group operation system with multiple outdoor units (Shielding wires and address setting are nec-

essary.)

<Examples of Transmission Cable Wiring>

N

 

M-NET Remote Controller (Fig. 6-2)

N

 

MA Remote Controller (Fig. 6-3)

<Wiring Method and Address Settings>
a.  Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.
b.  Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2 

and terminal S on the transmission cable block of the indoor unit (IC).

c.  Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the terminal 

block on the remote controller (RC).

d.  Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC).
e.  The jumper connector CN41 on the control panel does not change.
f.   Connect shield ground of the indoor units transmission line to the shield (S) terminal of (TB3) and also connect (S) terminal to screw 

C

 or 

D

 using attached lead wire. 

 

Connect shield ground of the line between outdoor units and the central control system transmission line to the shield (S) terminal of (TB7). 

g.  Set the address setting switch as follows.

Unit

Range

Setting Method

IC (Main)

01 to 50

Use the most recent address within the same group of  indoor units

IC (Sub) 

01 to 50

Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must 
be in sequence with the IC (Main)

Outdoor Unit

51 to 100

Use the most recent address of all the indoor units plus 50
*  The address automatically becomes “100” if it is set as “01 - 50”.

M-NET R/C (Main)

101 to 150

Set at an IC (Main) address within the same group plus 100

M-NET R/C (Sub)

151 to 200

Set at an IC (Main) address within the same group plus 150

MA R/C

Unnecessary address setting (Necessary main/sub setting)

h.  The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.
i. 

When connecting a PWFY unit

•  Do not perform the group settings for the PWFY unit and the indoor units.
•  The PWFY unit and a Lossnay unit cannot be set to operate at the same time.
•  Use a WMA remote controller for the PWFY unit.
For details, refer to the installation manual for the PWFY unit.

<Permissible Lengths>

1

 

M-NET Remote controller

•  Max length via outdoor units: 

L1+L2+L3+L4 and L1+L2+L3+L5 and L1+L2+L6+L7   500 m (1.25 mm2 or more)

•  Max transmission cable length:  L1 and L3+L4 and L3+L5 and L6 and L2+L6 and L7   200 m (1.25 mm2 or more)
•  Remote controller cable length:  ℓ1, ℓ2, ℓ2+ℓ3, ℓ4    10 m (0.5 to 1.25 mm2)
 

 If the length exceeds 10 m, use a 1.25 mm2 shielded wire.  The length of this section (L8) should be included in the calculation of the 

maximum length and overall length.

2

 

MA Remote controller

•  Max length via outdoor unit (M-NET cable): L1+L2+L3+L4 and L1+L2+L6+L7   500 m (1.25 mm2 or more)
•  Max transmission cable length (M-NET cable): L1 and L3+L4 and L6 and L2+L6 and L7   200 m (1.25 mm2 or more)
•  Remote controller cable length: m1 and m1+m2 +m3 and m1+m2+m3+m4    200 m (0.3 to 1.25 mm2)

6. Electrical work

M1

S

M2

M1

S

M2

TB3

TB7

L1 L2 L3 N

3.  MA Remote control cables

Kind of remote control cable

Sheathed 2-core cable (unshielded) CVV

Cable diameter

0.3 to 1.25 mm

(0.75 to 1.25 mm

2

)*

Remarks 

Within 200 m

* Connected with simple remote controller.

A

 :  Power source

B

 :  Transmission line

C

 :  Screw on the electrical component box

D

 :  Screw on the electrical component box

6.2.  Control box and connecting position of wiring
  

(Fig. 6-1)

1.  Connect the indoor unit transmission line to transmission terminal block (TB3), or 

connect the wiring between outdoor units or the wiring with the centralized control 
system to the centralized control terminal block (TB7).

 

When using shielded wiring, connect shield ground of the indoor unit transmission 
line to the screw (

C

 or 

D

) and connect shield ground of the line between outdoor 

units and the central control system transmission line to the shield (S) terminal of 
the centralized control terminal block (TB7) shield (S) terminal. In addition, in the 
case of outdoor units whose power supply connector CN41 has been replaced 
by CN40, the shield terminal (S) of terminal block (TB7) of the centralized control 
system should also be connected to the screw 

C

 or 

using attached lead wire.

2.  Conduit mounting plates (ø27) are being provided. Pass the power supply and 

transmission wires through the appropriate knock-out holes, then remove the 
knock-out piece from the bottom of the terminal box and connect the wires.

3.  Fix power source wiring to terminal box by using buffer bushing for tensile force 

(PG connection or the like).

Fig. 6-1

Содержание CITY MULTI PUMY-P100YHMB

Страница 1: ...INSTALACI N Para un uso correcto y seguro lea detalladamente este manual y el manual de instalaci n de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per...

Страница 2: ...result in an explosion and other hazards The use of any refrigerant other than that speci ed for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case thi...

Страница 3: ...rigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools sp...

Страница 4: ...unit within the outdoor unit s capacity if possible Only when all the indoor units are 1 5 kW models 12 indoor units can be connected to 1 outdoor unit 2 4 Connecting a PWFY Unit When using a PWFY uni...

Страница 5: ...air outlet guides for upward air ow 2 5 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 9 2 Obstacles at rear and above only Fig 2 1...

Страница 6: ...le structure it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An...

Страница 7: ...ealing is used refer to Table 3 for aring of R410A refrigerant pipes The size adjustment gauge can be used to con rm A measurements Warning When installing the unit securely connect the refrigerant pi...

Страница 8: ...ure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait ve minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem perature...

Страница 9: ...to outdoor unit 4 Give some allowance to wiring for electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power sour...

Страница 10: ...the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address setting Necessary main sub setting h The group setting operations a...

Страница 11: ...r If no earth leakage breaker is installed it may cause an electric shock Do not use anything other than breaker and fuse with correct capacity Using fuse and wire or copper wire with too large capaci...

Страница 12: ...carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refrigerant...

Страница 13: ...123 1 123 2 125 3 127 4 127 5 130 6 130 7 133 S TB3 TB7 6 2 R410A R410A HFC 1 6 R410A C1220 R410A Mitsubishi Electric 1 10 2002 96 IV R410A R410A GWP 1975...

Страница 14: ...124 1 1 1 1 2 20 1 3 1 4 12 B 1 5 R410A C1220 127 R22 127 R410A R410A R410A R410A...

Страница 15: ...5 12 1 2 4 PWFY PWFY PWFY 2 4 1 1 PWFY P100VM E AU PWFY P200VM E AU PWFY P100VM E BU PWFY PWFY 50 100 PWFY PUMY P100 1 PWFY 5 6 11 2 PUMY P125 1 PWFY 7 1 14 0 PUMY P140 1 PWFY 8 0 15 5 2 4 2 PWFY PUM...

Страница 16: ...300 200 1000 150 1000 300 1500 1500 500 1000 600 2000 150 1500 600 3000 500 1500 800 150 2 5 2 5 1 1 Fig 2 3 2 Fig 2 4 3 Fig 2 5 4 Fig 2 6 500 5 Fig 2 7 500 6 Fig 2 8 2 5 2 10 1 Fig 2 9 2 Fig 2 10 3 F...

Страница 17: ...A 2 Fig 2 17 B Fig 2 16 Fig 2 17 2 Fig 3 1 4 4 1 R410A 124 R410A C1220 R410A 15 50 63 140 6 35 0 8 9 52 0 8 12 7 0 8 15 88 1 0 3 Fig 3 1 M10 3 8 120 70 320 30 10 5 15 A 10 3 8 B C D 30 600 600 360 10...

Страница 18: ...D a b c d e 120 L A B C D e 80 B C D e 30 H 50 20 h 12 A a b c d e f 120 L A f 80 f 30 H 50 20 h 12 Fig 4 1 A B A B 3 Fig 4 3 A Fig 4 2 B Fig 4 2 O D A R410A R22 R407C 6 35 0 0 5 1 0 1 5 9 52 0 0 5 1...

Страница 19: ...1 2 4 3 Fig 4 4 D A B 1 2 3 4 4 4 20 25 200 250 5 4 4 1 A B C A B 2 1 0 5 5 2 G 2 1 5 15 2 G 3 4 15 41 5 2 G 3 1 C 0 01 0 1 2 G 4 2 3 4 5 1 Fig 4 6 1 1 4 2 2 Fig 4 7 1 4 6 35 4 5 9 52 10 2 A B C D E F...

Страница 20: ...35 10 3 25 c 6 35 10 4 20 d 6 35 20 9 52 A a 30 15 45 6 35 b c d 10 10 20 40 45 0 06 40 0 024 3 0 0 7 5 6 1 1 C 2 5 3 4 5 6 2 6 7 3 7 8 2 CN41 CN40 9 3 0 6 35 0 024 0 024 9 52 0 06 0 06 A A B C D Fig...

Страница 21: ...L6 L2 L6 L7 200 1 25 2 1 2 2 3 4 10 0 5 1 25 2 10 1 25 2 L8 2 MA M NET L1 L2 L3 L4 L1 L2 L6 L7 500 1 25 2 M NET L1 L3 L4 L6 L2 L6 L7 200 1 25 2 m1 m1 m2 m3 m1 m2 m3 m4 200 0 3 1 25 2 6 2 Fig 6 1 1 TB3...

Страница 22: ...1 A B A B A B A B M1M2 S TB3 M1M2S TB7 IC 51 M1M2 1 2 S TB5 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 MA 01 IC M1M2S TB5 03 IC M1M2S TB5 02 IC M1M2S TB5 04 IC M1M2S TB5 05 IC M1M2S T...

Страница 23: ...SW3 7 2 1 SW3 1 OFF DIP SW3 2 DIP SW3 1 DIP SW3 1 7 3 1 COOL TEST RUN 2 3 SW3 2 OFF SW3 1 ON 4 SW2 4 OFF ON 5 ON 6 0 0 1 0 1 2 5 SW3 1 OFF 7 SW2 4 ON OFF 8 1 2 SW2 4 ON OFF 3 SW3 1 ON SW3 2 ON OFF 4...

Страница 24: ...XBRIDGE MIDDLESEX UB8 1QQ UK Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residentia...

Отзывы: