2. Installation location

2.1. Refrigerant pipe

Refer to Fig. 4-1.

2.2.  Choosing the outdoor unit installation location

•  Avoid locations exposed to direct sunlight or other sources of heat.
•  Select a location from which noise emitted by the unit will not inconvenience neigh-

bors.

•  Select a location permitting easy wiring and pipe access to the power source and 

indoor unit.

•  Avoid locations where combustible gases may leak, be produced, flow, or accumu-

late.

•  Note that water may drain from the unit during operation.
•  Select a level location that can bear the weight and vibration of the unit.
•  Avoid locations where the unit can be covered by snow. In areas where heavy snow 

fall is anticipated, special precautions such as raising the installation location or 
installing a hood on the air intake must be taken to prevent the snow from block-
ing the air intake or blowing directly against it. This can reduce the airflow and a 
malfunction may result.

•  Avoid locations exposed to oil, steam, or sulfuric gas.
•  Use the transportation handles of the outdoor unit to transport the unit. If the unit 

is carried from the bottom, hands or fingers may be pinched.

2.3.  Outline dimensions (Outdoor unit) (Fig. 2-1)

Constraints on indoor unit installation

You should note that indoor units that can be connected to this outdoor unit are the 
following models. 
•  Indoor units with model numbers 15-140 (PUMY-P100:15-125) can be connected. 

Refer to the table 1 below for possible room, indoor unit combinations.

Verification

The rated capacity should be determined by observing the table below. The unit’s 
quantities are limited as shown in the following table 2. For the next step, make 
sure that the total rated capacity selected will stay in a range of 50% - 130% of the 
outdoor unit capacity.

•  PUMY-P100 

5.6 - 14.6 kW

•  PUMY-P125 

7.1 - 18.2 kW

•  PUMY-P140 

8.0 - 20.2 kW

Table 1 

Indoor unit type

15

20

25

32

40

50

63

71

80

100

125

140

Rated capacity
(Cooling) (kW)

1.7

2.2

2.8

3.6

4.5

5.6

7.1

8.0

9.0

11.2

14.0 16.0

Table 2 

Connectable indoor units quantities

PUMY-P100

1-8

PUMY-P125

1-10

PUMY-P140

 1-12*

Combinations in which the total capacity of indoor units exceeds the capacity of the 
outdoor unit will reduce the cooling capacity of each indoor unit below their rated 
cooling capacity. Thus, combine indoor units with an outdoor unit within the outdoor 
unit’s capacity, if possible.

*  Only when all the indoor units are 1.5 kW models, 12 indoor units can be connected 

to 1 outdoor unit.

2.4.  Connecting a PWFY Unit

When using a PWFY unit as an indoor unit, be aware of the following points 
because the PWFY unit is different from other indoor units.

2.4.1. Connection restrictions

•  Only 1 PWFY-P100VM-E-AU can be connected. PWFY-P200VM-E-AU and PWFY-

P100VM-E-BU cannot be connected.

•  The PWFY unit cannot be the only unit connected to an outdoor unit. Select an 

outdoor unit so that the total rated capacity of the indoor units, excluding the PWFY 
unit, is 50–100% of the outdoor unit capacity.

Limits for the total rated capacity of the indoor units when connecting a PWFY unit
•  PUMY-P100 (1 PWFY unit + Non-PWFY units [5.6–11.2 kW])
•  PUMY-P125 (1 PWFY unit + Non-PWFY units [7.1–14.0 kW])
•  PUMY-P140 (1 PWFY unit + Non-PWFY units [8.0–15.5 kW])

2.4.2.  Indoor unit specifications

When connecting a PWFY unit to a PUMY unit, the following specifications will 
change.
•  The PWFY unit can operate only in heating mode. The PWFY unit cannot operate 

in cooling mode. However, the indoor units other than the PWFY unit can operate 
in cooling mode.

•  The other indoor units cannot operate at the same time as the PWFY unit.
•  The operation of the PWFY unit has priority. When the PWFY unit is in the operation 

mode, the other indoor units will stop.

•  The temperature setting of the remote controller is the target value for the outlet 

water temperature.

2.4.3.  Switch settings (Fig. 2-2)

When connecting a PWFY unit to a PUMY unit, set DIP switches SW1-1, SW4-2, and 
SW4-6 of the PWFY unit to ON.

2.4.4. Test run

If the test run is carried out using the outdoor unit switches, the PWFY unit will 
not operate. Carry out the test run using the PWFY unit switches or the remote 
controller.
For information about carrying out the test run, refer to the data book or the service 
manual for the PWFY unit.

2.4.5.  Refrigerant collecting (Pump down)

Step 

 in the pump down procedure instructs the user to “operate all indoor units 

in cooling mode”. However, the PWFY unit will not operate in cooling mode.
Operate all of the indoor units, excluding the PWFY unit, in cooling mode.

Fig. 2-1

(mm)

950

330+30

1350

175

600

370

Table 3 PWFY unit specifications

Model

PWFY-P100VM-E-AU

Temp. range of 

Heating

Outdoor temp.

–15 to 21°C (DB), –15 to 15°C (WB)

Inlet Water temp.

10 to 45°C

Temp. range of 

Cooling

Outdoor temp.

Inlet Water temp.

SW1

1

2

3

4

5

6

7

8

9 10

ON

SW4

1

2

3

4

5

6

7

8

9 10

ON

Fig. 2-2

Содержание CITY MULTI PUMY-P100YHMB

Страница 1: ...INSTALACI N Para un uso correcto y seguro lea detalladamente este manual y el manual de instalaci n de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per...

Страница 2: ...result in an explosion and other hazards The use of any refrigerant other than that speci ed for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case thi...

Страница 3: ...rigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools sp...

Страница 4: ...unit within the outdoor unit s capacity if possible Only when all the indoor units are 1 5 kW models 12 indoor units can be connected to 1 outdoor unit 2 4 Connecting a PWFY Unit When using a PWFY uni...

Страница 5: ...air outlet guides for upward air ow 2 5 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 9 2 Obstacles at rear and above only Fig 2 1...

Страница 6: ...le structure it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An...

Страница 7: ...ealing is used refer to Table 3 for aring of R410A refrigerant pipes The size adjustment gauge can be used to con rm A measurements Warning When installing the unit securely connect the refrigerant pi...

Страница 8: ...ure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait ve minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem perature...

Страница 9: ...to outdoor unit 4 Give some allowance to wiring for electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power sour...

Страница 10: ...the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address setting Necessary main sub setting h The group setting operations a...

Страница 11: ...r If no earth leakage breaker is installed it may cause an electric shock Do not use anything other than breaker and fuse with correct capacity Using fuse and wire or copper wire with too large capaci...

Страница 12: ...carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refrigerant...

Страница 13: ...123 1 123 2 125 3 127 4 127 5 130 6 130 7 133 S TB3 TB7 6 2 R410A R410A HFC 1 6 R410A C1220 R410A Mitsubishi Electric 1 10 2002 96 IV R410A R410A GWP 1975...

Страница 14: ...124 1 1 1 1 2 20 1 3 1 4 12 B 1 5 R410A C1220 127 R22 127 R410A R410A R410A R410A...

Страница 15: ...5 12 1 2 4 PWFY PWFY PWFY 2 4 1 1 PWFY P100VM E AU PWFY P200VM E AU PWFY P100VM E BU PWFY PWFY 50 100 PWFY PUMY P100 1 PWFY 5 6 11 2 PUMY P125 1 PWFY 7 1 14 0 PUMY P140 1 PWFY 8 0 15 5 2 4 2 PWFY PUM...

Страница 16: ...300 200 1000 150 1000 300 1500 1500 500 1000 600 2000 150 1500 600 3000 500 1500 800 150 2 5 2 5 1 1 Fig 2 3 2 Fig 2 4 3 Fig 2 5 4 Fig 2 6 500 5 Fig 2 7 500 6 Fig 2 8 2 5 2 10 1 Fig 2 9 2 Fig 2 10 3 F...

Страница 17: ...A 2 Fig 2 17 B Fig 2 16 Fig 2 17 2 Fig 3 1 4 4 1 R410A 124 R410A C1220 R410A 15 50 63 140 6 35 0 8 9 52 0 8 12 7 0 8 15 88 1 0 3 Fig 3 1 M10 3 8 120 70 320 30 10 5 15 A 10 3 8 B C D 30 600 600 360 10...

Страница 18: ...D a b c d e 120 L A B C D e 80 B C D e 30 H 50 20 h 12 A a b c d e f 120 L A f 80 f 30 H 50 20 h 12 Fig 4 1 A B A B 3 Fig 4 3 A Fig 4 2 B Fig 4 2 O D A R410A R22 R407C 6 35 0 0 5 1 0 1 5 9 52 0 0 5 1...

Страница 19: ...1 2 4 3 Fig 4 4 D A B 1 2 3 4 4 4 20 25 200 250 5 4 4 1 A B C A B 2 1 0 5 5 2 G 2 1 5 15 2 G 3 4 15 41 5 2 G 3 1 C 0 01 0 1 2 G 4 2 3 4 5 1 Fig 4 6 1 1 4 2 2 Fig 4 7 1 4 6 35 4 5 9 52 10 2 A B C D E F...

Страница 20: ...35 10 3 25 c 6 35 10 4 20 d 6 35 20 9 52 A a 30 15 45 6 35 b c d 10 10 20 40 45 0 06 40 0 024 3 0 0 7 5 6 1 1 C 2 5 3 4 5 6 2 6 7 3 7 8 2 CN41 CN40 9 3 0 6 35 0 024 0 024 9 52 0 06 0 06 A A B C D Fig...

Страница 21: ...L6 L2 L6 L7 200 1 25 2 1 2 2 3 4 10 0 5 1 25 2 10 1 25 2 L8 2 MA M NET L1 L2 L3 L4 L1 L2 L6 L7 500 1 25 2 M NET L1 L3 L4 L6 L2 L6 L7 200 1 25 2 m1 m1 m2 m3 m1 m2 m3 m4 200 0 3 1 25 2 6 2 Fig 6 1 1 TB3...

Страница 22: ...1 A B A B A B A B M1M2 S TB3 M1M2S TB7 IC 51 M1M2 1 2 S TB5 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 MA 01 IC M1M2S TB5 03 IC M1M2S TB5 02 IC M1M2S TB5 04 IC M1M2S TB5 05 IC M1M2S T...

Страница 23: ...SW3 7 2 1 SW3 1 OFF DIP SW3 2 DIP SW3 1 DIP SW3 1 7 3 1 COOL TEST RUN 2 3 SW3 2 OFF SW3 1 ON 4 SW2 4 OFF ON 5 ON 6 0 0 1 0 1 2 5 SW3 1 OFF 7 SW2 4 ON OFF 8 1 2 SW2 4 ON OFF 3 SW3 1 ON SW3 2 ON OFF 4...

Страница 24: ...XBRIDGE MIDDLESEX UB8 1QQ UK Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residentia...

Отзывы: