background image

7

4.2.  Connecting pipes (Fig. 4-2)

Fig. 4-1 is a sample of piping system.
•  When commercially available copper pipes are used, wrap liquid and gas pipes 

with commercially available insulation materials (heat-resistant to 100°C or more, 
thickness of 12 mm or more).

•  The indoor parts of the drain pipe should be wrapped with polyethylene foam insula-

tion materials (specific gravity of 0.03, thickness of 9 mm or more).

•  Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening 

flare nut. 

A

•  Use two wrenches to tighten piping connections. 

B

•  Use leak detector or soapy water to check for gas leaks after connections are 

completed. 

•  Apply refrigerating machine oil over the entire flare seat surface. 

C

•  Use the flare nuts for the following pipe size. 

D

Indoor unit

Outdoor unit

15-50

63-140

100-140

Gas side

Pipe size (mm)

ø12.7

ø15.88

ø15.88

Liquid side

Pipe size (mm)

ø6.35

ø9.52

ø9.52

•  When bending the pipes, be careful not to break them. Bend radius of 100 mm to 

150 mm is sufficient.

•  Make sure the pipes do not contact the compressor. Abnormal noise or vibration 

may result.

1

 Pipes must be connected starting from the indoor unit.

 

Flare nuts must be tightened with a torque wrench.

2

 Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil 

(Applied on site). 

•  When usual pipe sealing is used, refer to Table 3 for flaring of R410A refrigerant 

pipes.

  The size adjustment gauge can be used to confirm A measurements.

 Warning:

When installing the unit, securely connect the refrigerant pipes before starting 
the compressor.

A  

(mm)

È

 Liquid pipe

É 

Gas pipe

PUMY-P100-140

ø9.52

ø15.88

B, C, D 

(mm)

Ê

 Total capacity of indoor units

È

 Liquid pipe

É

 Gas pipe

ø9.52

ø15.88

a, b, c, d, e, f 

(mm)

Ë

 Model number

È

 Liquid pipe

É

 Gas pipe

15, 20, 25, 32, 40, 50

ø6.35

ø12.7

63, 80, 100, 125, 140

ø9.52

ø15.88

Ì

 Branch kit model

CMY-Y62-G-E

Í

 4-Branching header

Î

 8-Branching header

CMY-Y64-G-E

CMY-Y68-G-E

  Flare cutting dimensions

B  

Flare nut tightening torque

A

  Die

B

  Copper pipe

Fig. 4-2

A

Fig. 4-3

A

 (Fig. 4-2)

B

 (Fig. 4-2)

Table 3 (Fig. 4-3)

4.  Installing the refrigerant piping

A

H

B

C

L

D

e

a

h

b

c

d

A

a

b

c

d

e

f

H

h

L

A

 :  Outdoor Unit

B

 :  First Branch

C

 :  Indoor unit

D

 :  Cap

A+B+C+D+a+b+c+d+e   120 m

L = A+B+C+D+e   80 m

ℓ = B+C+D+e   30 m

H   50 m (Outdoor lower H   20 m)

h   12 m

A+a+b+c+d+e+f   120 m

L = A+f   80 m, ℓ = f   30 m

H   50 m (Outdoor lower H   20 m)

h   12 m

Fig. 4-1

90°± 0.5°

øA

45°± 2°

R0.4 - R0.8

Copper pipe O.D. (mm)

A (mm)

Flare tool for R410A

Flare tool for R22·R407C

Clutch type

ø6.35 (1/4″)

0 - 0.5

1.0 - 1.5

ø9.52 (3/8″)

0 - 0.5

1.0 - 1.5

ø12.7 (1/2″)

0 - 0.5

1.0 - 1.5

ø15.88 (5/8″)

0 - 0.5

1.0 - 1.5

ø19.05 (3/4″)

0 - 0.5

1.0 - 1.5

Copper pipe O.D. 

(mm)

Flare dimensions 

øA dimensions (mm) 

ø6.35

8.7 - 9.1

ø9.52

12.8 - 13.2

ø12.7

16.2 - 16.6

ø15.88

19.3 - 19.7

Copper pipe O.D. 

(mm)

Flare unt O.D. 

(mm) 

Tightening torque 

(N·m)

ø6.35

17

14 - 18

ø6.35

22

34 - 42

ø9.52

22

34 - 42

ø12.7

26

49 - 61

ø12.7

29

68 - 82

ø15.88

29

68 - 82

ø15.88

36

100 - 120

Содержание CITY MULTI PUMY-P100YHMB

Страница 1: ...INSTALACI N Para un uso correcto y seguro lea detalladamente este manual y el manual de instalaci n de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per...

Страница 2: ...result in an explosion and other hazards The use of any refrigerant other than that speci ed for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case thi...

Страница 3: ...rigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools sp...

Страница 4: ...unit within the outdoor unit s capacity if possible Only when all the indoor units are 1 5 kW models 12 indoor units can be connected to 1 outdoor unit 2 4 Connecting a PWFY Unit When using a PWFY uni...

Страница 5: ...air outlet guides for upward air ow 2 5 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 9 2 Obstacles at rear and above only Fig 2 1...

Страница 6: ...le structure it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An...

Страница 7: ...ealing is used refer to Table 3 for aring of R410A refrigerant pipes The size adjustment gauge can be used to con rm A measurements Warning When installing the unit securely connect the refrigerant pi...

Страница 8: ...ure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait ve minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem perature...

Страница 9: ...to outdoor unit 4 Give some allowance to wiring for electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power sour...

Страница 10: ...the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address setting Necessary main sub setting h The group setting operations a...

Страница 11: ...r If no earth leakage breaker is installed it may cause an electric shock Do not use anything other than breaker and fuse with correct capacity Using fuse and wire or copper wire with too large capaci...

Страница 12: ...carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refrigerant...

Страница 13: ...123 1 123 2 125 3 127 4 127 5 130 6 130 7 133 S TB3 TB7 6 2 R410A R410A HFC 1 6 R410A C1220 R410A Mitsubishi Electric 1 10 2002 96 IV R410A R410A GWP 1975...

Страница 14: ...124 1 1 1 1 2 20 1 3 1 4 12 B 1 5 R410A C1220 127 R22 127 R410A R410A R410A R410A...

Страница 15: ...5 12 1 2 4 PWFY PWFY PWFY 2 4 1 1 PWFY P100VM E AU PWFY P200VM E AU PWFY P100VM E BU PWFY PWFY 50 100 PWFY PUMY P100 1 PWFY 5 6 11 2 PUMY P125 1 PWFY 7 1 14 0 PUMY P140 1 PWFY 8 0 15 5 2 4 2 PWFY PUM...

Страница 16: ...300 200 1000 150 1000 300 1500 1500 500 1000 600 2000 150 1500 600 3000 500 1500 800 150 2 5 2 5 1 1 Fig 2 3 2 Fig 2 4 3 Fig 2 5 4 Fig 2 6 500 5 Fig 2 7 500 6 Fig 2 8 2 5 2 10 1 Fig 2 9 2 Fig 2 10 3 F...

Страница 17: ...A 2 Fig 2 17 B Fig 2 16 Fig 2 17 2 Fig 3 1 4 4 1 R410A 124 R410A C1220 R410A 15 50 63 140 6 35 0 8 9 52 0 8 12 7 0 8 15 88 1 0 3 Fig 3 1 M10 3 8 120 70 320 30 10 5 15 A 10 3 8 B C D 30 600 600 360 10...

Страница 18: ...D a b c d e 120 L A B C D e 80 B C D e 30 H 50 20 h 12 A a b c d e f 120 L A f 80 f 30 H 50 20 h 12 Fig 4 1 A B A B 3 Fig 4 3 A Fig 4 2 B Fig 4 2 O D A R410A R22 R407C 6 35 0 0 5 1 0 1 5 9 52 0 0 5 1...

Страница 19: ...1 2 4 3 Fig 4 4 D A B 1 2 3 4 4 4 20 25 200 250 5 4 4 1 A B C A B 2 1 0 5 5 2 G 2 1 5 15 2 G 3 4 15 41 5 2 G 3 1 C 0 01 0 1 2 G 4 2 3 4 5 1 Fig 4 6 1 1 4 2 2 Fig 4 7 1 4 6 35 4 5 9 52 10 2 A B C D E F...

Страница 20: ...35 10 3 25 c 6 35 10 4 20 d 6 35 20 9 52 A a 30 15 45 6 35 b c d 10 10 20 40 45 0 06 40 0 024 3 0 0 7 5 6 1 1 C 2 5 3 4 5 6 2 6 7 3 7 8 2 CN41 CN40 9 3 0 6 35 0 024 0 024 9 52 0 06 0 06 A A B C D Fig...

Страница 21: ...L6 L2 L6 L7 200 1 25 2 1 2 2 3 4 10 0 5 1 25 2 10 1 25 2 L8 2 MA M NET L1 L2 L3 L4 L1 L2 L6 L7 500 1 25 2 M NET L1 L3 L4 L6 L2 L6 L7 200 1 25 2 m1 m1 m2 m3 m1 m2 m3 m4 200 0 3 1 25 2 6 2 Fig 6 1 1 TB3...

Страница 22: ...1 A B A B A B A B M1M2 S TB3 M1M2S TB7 IC 51 M1M2 1 2 S TB5 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 MA 01 IC M1M2S TB5 03 IC M1M2S TB5 02 IC M1M2S TB5 04 IC M1M2S TB5 05 IC M1M2S T...

Страница 23: ...SW3 7 2 1 SW3 1 OFF DIP SW3 2 DIP SW3 1 DIP SW3 1 7 3 1 COOL TEST RUN 2 3 SW3 2 OFF SW3 1 ON 4 SW2 4 OFF ON 5 ON 6 0 0 1 0 1 2 5 SW3 1 OFF 7 SW2 4 ON OFF 8 1 2 SW2 4 ON OFF 3 SW3 1 ON SW3 2 ON OFF 4...

Страница 24: ...XBRIDGE MIDDLESEX UB8 1QQ UK Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residentia...

Отзывы: