7.2. Test run

7.2.1.  Using remote controller 

Refer to the indoor unit installation manual.

•  Be sure to perform the test run for each indoor unit. Make sure each indoor 

unit operates properly following the installation manual attached to the unit.

•  If you perform the test run for all indoor units at once, you cannot detect any 

erroneous connection, if any, of the refrigerant pipes and the connecting 
wires.

* The compressor operation is not available for 3 minutes at least after the 

power is supplied.

•  The compressor can emit noise just after turn on the power supply or in case 

of low outside air temperature.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor 
will not operate for 3 minutes to protect the air conditioner.

7.2.2.  Using SW3 in outdoor unit

Note:
In case of the test run from outdoor unit, all indoor units operate. Therefore, 
you can not detect any erroneous connection of refrigerant pipes and the 
connecting wires. If it aims at detection of any erroneous connection, be sure 
to carry out the test run from remote controller with reference to “7.2.1 Using 
remote controller.”

SW3-1

ON

Cooling operation

SW3-2

OFF

SW3-1

ON

Heating operation

SW3-2

ON

*  After performing the test run, set SW3-1 to OFF.
•  A few seconds after the compressor starts, a clanging noise may be heard from 

the inside of the outdoor unit. The noise is coming from the check valve due to the 
small difference in pressure in the pipes. The unit is not faulty.

The test run operation mode cannot be changed by DIP switch SW3-2 during 
the test run. (To change the test run operation mode during the test run, stop 
the test run by DIP switch SW3-1. After changing the test run operation mode, 
resume the test run by switch SW3-1.)

7. Test run

7.3.  Refrigerant collecting (Pump down)

Before removing air conditioners for transfer to another location, always close the 
stop valve (for both liquid and gas pipes) located at the outdoor unit, then remove 
the indoor and outdoor units. At this time, the refrigerant in the indoor unit will be dis-
charged. To minimize the refrigerant discharged, a pump down operation is required. 
This operation collects the refrigerant present inside the air conditioner and sends it 
into the heat exchanger located in the outdoor unit.

Pump down procedure

1

  Operate all indoor units in cooling mode and check that the operation mode has 

changed to “COOL”. (Set the units so that cooling operation mode is activated 
during the pump down operation (when the TEST RUN button is pressed).)

2

  Connect a gauge manifold valve (with pressure gauge) to the stop valve of the 

gas pipe, to enable measurement of refrigerant pressure.

3

  After setting the outdoor service switch SW3-2 to OFF, set the switch SW3-1 to 

ON. (The unit will start in cooling mode.)

4

  After the cooling operation has been carried out for approximately five minutes, 

set the outdoor service switch SW2-4 (pump down switch) from OFF to ON. 

5

  Close the stop valve on the liquid pipe, with the cooling operation still ON. (Pump 

down operation will start.)

6

  When the reading of the pressure gauge reaches 0 to 0.1 MPa (0 to 1 kg/cm

2

G) or 

when approximately 5 minutes have elapsed following the start of the pump down 
operation, fully close the stop valve on the gas pipe and stop the air conditioner 
by setting the switch SW3-1 to OFF immediately.

7

  Set the outdoor service switch SW2-4 from ON to OFF.

8

  Remove the gauge manifold valve and put the cap back onto each stop valve.

Note:

1

  Never carry out pump down operation if the amount of refrigerant inside 

the indoor unit is larger than the amount of charge-less refrigerant.

 

Carrying out a pump down operation when the amount of refrigerant exceeds 
the amount of charge-less refrigerant will cause an extreme pressure rise 
and may result in an accident.

2

  Do not continue to operate for a long time with the switch SW2-4 set to 

ON.

 

Make sure to switch it to OFF after pump down is completed.

3

  Test run can be carried out when the test run switch SW3-1 is ON. Switch 

SW3-2 is used to operating mode selection. (ON: Heating, OFF: Cooling)

4

  Time required for a pump down operation is three to five minutes after the 

stop valve on the liquid pipe has been closed. (It depends on the ambient 
temperature and amount of refrigerant inside the indoor unit.)

5

  Ensure that the reading of the pressure gauge does not drop below 0 MPa 

(0 kg/cm

2

G). If it drops 0 MPa (0 kg/cm

2

G) (i.e. vacuum is created), air will 

be drawn into the unit if there are any loose connections.

6

  Even if the reading of the pressure gauge does not drop below 0 MPa (0 

kg/cm

2

G), always stop the pump down operation within approximately five 

minutes after the stop valve on the liquid pipe has been fully closed.

 Warning:

When pumping down the refrigerant, stop the compressor before disconnect-
ing the refrigerant pipes. The compressor may burst if air etc. get into it.

7.1.  Before test run

► After completing installation and the wiring and piping of the indoor and 

outdoor units, check for refrigerant leakage, looseness in the power supply 
or control wiring, wrong polarity, and no disconnection of one phase in the 
supply.

►  Use a 500-volt M-ohm tester to check that the resistance between the power 

supply terminals and ground is at least 1 MΩ.

►  Do not carry out this test on the control wiring (low voltage circuit) termi-

nals.
 Warning:

Do not use the air conditioner if the insulation resistance is less than 1 MΩ.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended 
period, the insulation resistance will drop below 1 MΩ due to refrigerant accumulating 
in the compressor. This is not a malfunction. Perform the following procedures.
1.  Remove the wires from the compressor and measure the insulation resistance of 

the compressor.

2.  If the insulation resistance is below 1 MΩ, the compressor is faulty or the resist-

ance dropped due the accumulation of refrigerant in the compressor.

3.  After connecting the wires to the compressor, the compressor will start to warm 

up after power is supplied. After supplying power for the times indicated below, 
measure the insulation resistance again.

 

•  The insulation resistance drops due to accumulation of refrigerant in the com-

pressor. The resistance will rise above 1 MΩ after the compressor is warmed 
up for four hours.

 

 

(The time necessary to warm up the compressor varies according to atmospheric 
conditions and refrigerant accumulation.)

 

•  To operate the compressor with refrigerant accumulated in the compressor, the 

compressor must be warmed up at least 12 hours to prevent breakdown.

4.  If the insulation resistance rises above 1 MΩ, the compressor is not faulty.

  Caution:

  The compressor will not operate unless the power supply phase connection 

is correct.

•  Turn on the power at least 12 hours before starting operation.

-  Starting operation immediately after turning on the main power switch can result 

in severe damage to internal parts. Keep the power switch turned on during the 
operational season.

►  The followings must be checked as well.

•  The outdoor unit is not faulty. LED on the control board of the outdoor unit flash 

when the outdoor unit is faulty.

•  Both the gas and liquid stop valves are completely open.

Содержание CITY MULTI PUMY-P100YHMB

Страница 1: ...INSTALACI N Para un uso correcto y seguro lea detalladamente este manual y el manual de instalaci n de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per...

Страница 2: ...result in an explosion and other hazards The use of any refrigerant other than that speci ed for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case thi...

Страница 3: ...rigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools sp...

Страница 4: ...unit within the outdoor unit s capacity if possible Only when all the indoor units are 1 5 kW models 12 indoor units can be connected to 1 outdoor unit 2 4 Connecting a PWFY Unit When using a PWFY uni...

Страница 5: ...air outlet guides for upward air ow 2 5 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 9 2 Obstacles at rear and above only Fig 2 1...

Страница 6: ...le structure it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An...

Страница 7: ...ealing is used refer to Table 3 for aring of R410A refrigerant pipes The size adjustment gauge can be used to con rm A measurements Warning When installing the unit securely connect the refrigerant pi...

Страница 8: ...ure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait ve minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem perature...

Страница 9: ...to outdoor unit 4 Give some allowance to wiring for electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power sour...

Страница 10: ...the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address setting Necessary main sub setting h The group setting operations a...

Страница 11: ...r If no earth leakage breaker is installed it may cause an electric shock Do not use anything other than breaker and fuse with correct capacity Using fuse and wire or copper wire with too large capaci...

Страница 12: ...carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refrigerant...

Страница 13: ...123 1 123 2 125 3 127 4 127 5 130 6 130 7 133 S TB3 TB7 6 2 R410A R410A HFC 1 6 R410A C1220 R410A Mitsubishi Electric 1 10 2002 96 IV R410A R410A GWP 1975...

Страница 14: ...124 1 1 1 1 2 20 1 3 1 4 12 B 1 5 R410A C1220 127 R22 127 R410A R410A R410A R410A...

Страница 15: ...5 12 1 2 4 PWFY PWFY PWFY 2 4 1 1 PWFY P100VM E AU PWFY P200VM E AU PWFY P100VM E BU PWFY PWFY 50 100 PWFY PUMY P100 1 PWFY 5 6 11 2 PUMY P125 1 PWFY 7 1 14 0 PUMY P140 1 PWFY 8 0 15 5 2 4 2 PWFY PUM...

Страница 16: ...300 200 1000 150 1000 300 1500 1500 500 1000 600 2000 150 1500 600 3000 500 1500 800 150 2 5 2 5 1 1 Fig 2 3 2 Fig 2 4 3 Fig 2 5 4 Fig 2 6 500 5 Fig 2 7 500 6 Fig 2 8 2 5 2 10 1 Fig 2 9 2 Fig 2 10 3 F...

Страница 17: ...A 2 Fig 2 17 B Fig 2 16 Fig 2 17 2 Fig 3 1 4 4 1 R410A 124 R410A C1220 R410A 15 50 63 140 6 35 0 8 9 52 0 8 12 7 0 8 15 88 1 0 3 Fig 3 1 M10 3 8 120 70 320 30 10 5 15 A 10 3 8 B C D 30 600 600 360 10...

Страница 18: ...D a b c d e 120 L A B C D e 80 B C D e 30 H 50 20 h 12 A a b c d e f 120 L A f 80 f 30 H 50 20 h 12 Fig 4 1 A B A B 3 Fig 4 3 A Fig 4 2 B Fig 4 2 O D A R410A R22 R407C 6 35 0 0 5 1 0 1 5 9 52 0 0 5 1...

Страница 19: ...1 2 4 3 Fig 4 4 D A B 1 2 3 4 4 4 20 25 200 250 5 4 4 1 A B C A B 2 1 0 5 5 2 G 2 1 5 15 2 G 3 4 15 41 5 2 G 3 1 C 0 01 0 1 2 G 4 2 3 4 5 1 Fig 4 6 1 1 4 2 2 Fig 4 7 1 4 6 35 4 5 9 52 10 2 A B C D E F...

Страница 20: ...35 10 3 25 c 6 35 10 4 20 d 6 35 20 9 52 A a 30 15 45 6 35 b c d 10 10 20 40 45 0 06 40 0 024 3 0 0 7 5 6 1 1 C 2 5 3 4 5 6 2 6 7 3 7 8 2 CN41 CN40 9 3 0 6 35 0 024 0 024 9 52 0 06 0 06 A A B C D Fig...

Страница 21: ...L6 L2 L6 L7 200 1 25 2 1 2 2 3 4 10 0 5 1 25 2 10 1 25 2 L8 2 MA M NET L1 L2 L3 L4 L1 L2 L6 L7 500 1 25 2 M NET L1 L3 L4 L6 L2 L6 L7 200 1 25 2 m1 m1 m2 m3 m1 m2 m3 m4 200 0 3 1 25 2 6 2 Fig 6 1 1 TB3...

Страница 22: ...1 A B A B A B A B M1M2 S TB3 M1M2S TB7 IC 51 M1M2 1 2 S TB5 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 MA 01 IC M1M2S TB5 03 IC M1M2S TB5 02 IC M1M2S TB5 04 IC M1M2S TB5 05 IC M1M2S T...

Страница 23: ...SW3 7 2 1 SW3 1 OFF DIP SW3 2 DIP SW3 1 DIP SW3 1 7 3 1 COOL TEST RUN 2 3 SW3 2 OFF SW3 1 ON 4 SW2 4 OFF ON 5 ON 6 0 0 1 0 1 2 5 SW3 1 OFF 7 SW2 4 ON OFF 8 1 2 SW2 4 ON OFF 3 SW3 1 ON SW3 2 ON OFF 4...

Страница 24: ...XBRIDGE MIDDLESEX UB8 1QQ UK Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residentia...

Отзывы: