Control
‘19 • HM-T-340
Default value: 55 °C
mixing valve amplifier
Setting range: 0.1 – 10.0
Default value: 1.0
mixing valve step delay
Setting range: 10 – 300 s
Default values: 30 s
Make settings for the hot water comfort here.
See the accessory installation instructions for function
description.
activating imm heater:
The immersion heater is activated
here if installed in the water heater.
activ. imm heat in heat mode:
Activate here whether the
immersion heater in the tank (required if the alternative above
is activated) will be permitted to charge hot water, if the
compressors in the heat pump prioritise heating.
activating the mixing valve:
Activate here whether a mixer
valve for limiting the temperature of hot water from the water
heater is installed.
If this alternative has been activated, you can set the outgoing
hot water temperature, shunt amplifi cation and shunt waiting
time for the mixer valve.
outgoing hot water:
Set the temperature at which the
mixing valve is to restrict hot water from the water heater.
Menu 5.3.20 - flow sensor
EMK 500
flow sensor
flow sensor 5.3.20
flow sensor
Setting option: EMK 500, EMK 310 / 300, EMK 150
Factory setting: EMK 500
Here you select which flow sensor is used for the energy
measurement.
that you have selected. If this function is activated, you can set
"cooling flow temp. at +20°C" and "cooling flow temp. at
+40°C" for each climate system where the function is
activated.
CAUTION
This setting option only appears if "cooling permitted" is
activated in menu 5.11.1.1.
The shunt amplifi cation and shunt waiting time for the diff erent
extra climate systems that are installed are also set here.
See the accessory installation instructions for function
description.
Menu 5.3.6 - step controlled add. heat
start addition
Setting range: 0 – 2000 GM
Default values: 400 GM
diff. between additional steps
Setting range: 0 – 1000 GM
Default values: 30 GM
max step
Setting range
(binary stepping deactivated): 0 – 3
Setting range
(binary stepping activated): 0 – 7
Default value: 3
binary stepping
Setting range: on/off
Factory setting: off
Make settings for step controlled addition here. Step controlled
addition is for example an external electric boiler.
It is possible, for example, to select when the additional heat is
to start, to set the maximum number of permitted steps and
whether binary stepping is to be used.
When binary stepping is deactivated (off ), the settings refer to
linear stepping.
See the accessory installation instructions for function
description.
Menu 5.3.8 - hot water comfort
activating imm heater
Setting range: on/off
Factory setting: off
activ. imm heat in heat mode
Setting range: on/off
Factory setting: off
activating the mixing valve
Setting range: on/off
Factory setting: off
outgoing hot water
Setting range: 40 – 65 °C
See the accessory installation instructions for function descrip-
tion.
Control
- 165 -
Содержание FDCW100VNX-A
Страница 7: ... 5 Technical data 19 HM T 340 Technical data ...
Страница 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Страница 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Страница 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Страница 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Страница 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Страница 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Страница 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Страница 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Страница 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Страница 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Страница 63: ... 61 Technical data 19 HM T 340 Electrical circuit diagram INDOOR UNIT HSB INDOOR UNIT HSB RC HY40 W sheet 5 ...
Страница 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Страница 65: ...Installation 19 HM T 340 Installation 63 ...
Страница 133: ...Control 19 HM T 340 Control 131 ...
Страница 170: ... 168 Service 19 HM T 340 Service ...
Страница 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Страница 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Страница 290: ... 285 Components 19 HM T 340 Components ...
Страница 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Страница 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Страница 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Страница 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Страница 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...