Control
'19 • HM-T-340
Menu 4.9 - advanced
Menu "advanced" has orange text and is intended for the
advanced user. This menu has several sub-menus.
advanced
4.9
op. prioritisation
auto mode setting
degree minute setting
factory setting user
schedule blocking
off
Menu 4.9.1 - op. prioritisation
op. prioritisation
4.9.1
min
min
min
hot water
heating
pool
30
30
30
op. prioritisation
Setting range: 0 – 180 min
Default value: 30 min
Choose here how long the installation should work with each
requirement if there are several requirements at the same time.
If there is only one requirement the installation only works
with that requirement.
The indicator marks where in the cycle the installation is.
If 0 minutes is selected it means that requirement is not
prioritised, but will only be activated when there is no other
requirement.
Menu 4.9.2 - auto mode setting
start cooling
stop heating
stop additional heat
filtering time
°C
°C
°C
hrs
auto mode setting
4.9.2
start cooling (accessory auto mode setting
required)
Setting range: 15 – 40 °C
Factory setting: 25
stop heating
Setting range: -20 – 40 °C
Default values: 17
stop additional heat
Setting range: -25 – 40 °C
Factory setting: 5
filtering time
Setting range: 0 – 48 h
Default value: 24 h
When the operating mode is set to "auto", the control module
selects when start and stop of additional heat and heat
production is permitted, depending on the average outdoor
temperature. If the heat pump has the integrated cooling
function and it is activated in the menu you can also select the
start temperature for cooling.
Select the average outdoor temperatures in this menu.
You can also set the time over which (filtering time) the
average temperature is calculated. If you select 0, the present
outdoor temperature is used.
CAUTION
It cannot be set "stop additional heat" higher than "stop
heating".
CAUTION
In systems where heating and cooling share the same pipes
"stop heating" cannot be set higher than "start cooling" if
there is not a cooling/heating sensor.
Menu 4.9.3 - degree minute setting
current value
start compressor
start diff additional heat
diff. between additional steps
DM
DM
DM
DM
degree minute setting
4.9.3
step difference compressors
DM
current value
Setting range: -3000 – 3000
start compressor
Setting range: -1000 – -30
Default value: -60
step difference compressors (RC-HY40
-W/HMA-S
only)
Setting range: 10 – 2000
Default value: 60
start diff additional heat
Setting range: 100 – 2000
Control
- 158 -
#
Содержание FDCW100VNX-A
Страница 7: ... 5 Technical data 19 HM T 340 Technical data ...
Страница 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Страница 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Страница 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Страница 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Страница 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Страница 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Страница 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Страница 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Страница 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Страница 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Страница 63: ... 61 Technical data 19 HM T 340 Electrical circuit diagram INDOOR UNIT HSB INDOOR UNIT HSB RC HY40 W sheet 5 ...
Страница 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Страница 65: ...Installation 19 HM T 340 Installation 63 ...
Страница 133: ...Control 19 HM T 340 Control 131 ...
Страница 170: ... 168 Service 19 HM T 340 Service ...
Страница 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Страница 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Страница 290: ... 285 Components 19 HM T 340 Components ...
Страница 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Страница 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Страница 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Страница 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Страница 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...