Control
'19 • HM-T-340
Menu 5.1.3 - max diff flow line temp.
max diff compressor
Setting range: 1 – 25 °C
Default value: 10 °C
max diff addition
Setting range: 1 – 24 °C
Default value: 7 °C
Here you set the maximum permitted difference between the
calculated and actual supply temperature during compressor
mode and add. heat mode. Max diff . additional heat can never
exceed max diff . compressor
max diff compressor
When the current supply temperature
deviates
from the set
value compared to that calculated, the heat pump is forced to
stop irrespective of the degreeminute value.
If the current supply temperature exceeds the calculated fl ow
temperature plus the set value, the degree minute value is set to
0. The compressor in the heat pump stops when there is only a
heating demand.
max diff addition
If "addition” is selected and activated in menu 4.2 and the
present supply temp
exceeds
the calculated temperature plus
the set value, the additional heat is forced to stop.
Menu 5.1.4 - alarm actions
Select how to control the heat pump in the event of an alarm.
You can choose to stop producing hot water and/or reduce the
room temperature.
CAUTION
If no alarm action is selected, it can result in
higher energy consumption in the event of an
alarm.
Menu 5.1.12 - addition
add type: step controlled
max step
Setting range (binary stepping deactivated): 0 – 3
Setting range (binary stepping activated): 0 – 7
Default value: 3
fuse size
Setting range: 1 – 200 A
Factory setting: 16 A
You can set the maximum number of permitted additional
heat steps, if there is internal additional heat in the tank (only
accessible if the additional heat is positioned after QN10),
whether binary stepping is to be used and the size of the
fuse.
<Add. Type: shu
n
t controlled (RC-HY40
-W
only)>
prioritised additional heat
Setting range: on/off
Factory setting: off
minimum running time
Setting range: 0 – 48 h
Default value: 12 h
min temp.
Setting range: 5 – 90 °C
Default value: 55 °C
mixing valve amplifier
Setting range: 0.1 – 10.0
Default value: 1.0
mixing valve step delay
Setting range: 10 – 300 s
Default values: 30 s
fuse size
Setting range: 1 – 200 A
Factory setting: 16 A
transformation ratio
Setting range: 300 – 3000
Factory setting: 300
Select this option if shunt controlled additional heat is
connected.
Set when the addition is to start, the minimum run time and the
minimum temperature for external addition with shunt here.
External addition with shunt is for example a wood/oil/gas/
pellet boiler.
You can set shunt valve amplifi cation and shunt valve waiting
time.
Selecting "prioritised additional heat" uses the heat from the
external additional heat instead of the heat pump.
The shunt valve is regulated as long as heat is available,
otherwise the shunt valve is closed.
TIP
See the accessory installation instructions for function
description.
Menu 5.1.14 - flow set. climate system
presettings
Setting range: radiator, fl oor heat., rad. + fl oor heat.
Default value: radiator
Setting range DOT: -40.0 – 20.0 °C
The factory setting of DOT value depends on the country
that has been given for the product's location.
The example below refers to Sweden.
Factory setting DOT: -20.0 °C
own setting
Setting range dT at DOT: 0.0 – 25.0
Control
- 162 -
#
Содержание FDCW100VNX-A
Страница 7: ... 5 Technical data 19 HM T 340 Technical data ...
Страница 36: ... 34 Technical data 19 HM T 340 Dimensions FDCW71VNX A Meaning of symbol ...
Страница 38: ... 36 Technical data 19 HM T 340 FDCW140VNX A Meaning of symbol Dimensions ...
Страница 41: ... 39 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 42: ... 40 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 43: ... 41 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 44: ... 42 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 45: ... 43 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 46: ... 44 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 47: ... 45 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 48: ... 46 Technical data 19 HM T 340 Electrical circuit diagram ...
Страница 49: ... 47 Technical data 19 HM T 340 Electrical circuit diagram Split box HSB60 W ...
Страница 50: ... 48 Technical data 19 HM T 340 HSB100 Electrical circuit diagram ...
Страница 51: ... 49 Technical data 19 HM T 340 HSB140 Electrical circuit diagram ...
Страница 52: ... 50 Technical data 19 HM T 340 Electrical circuit diagram Outdoor units FDCW60VNX A ...
Страница 57: ... 55 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY20 W sheet 3 ...
Страница 58: ... 56 Technical data 19 HM T 340 Electrical circuit diagram RC HY20 W sheet 4 ...
Страница 61: ... 59 Technical data 19 HM T 340 Electrical circuit diagram POWER SOURCE RC HY40 W sheet 3 ...
Страница 62: ... 60 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 4 ...
Страница 63: ... 61 Technical data 19 HM T 340 Electrical circuit diagram INDOOR UNIT HSB INDOOR UNIT HSB RC HY40 W sheet 5 ...
Страница 64: ... 62 Technical data 19 HM T 340 Electrical circuit diagram RC HY40 W sheet 6 ...
Страница 65: ...Installation 19 HM T 340 Installation 63 ...
Страница 133: ...Control 19 HM T 340 Control 131 ...
Страница 170: ... 168 Service 19 HM T 340 Service ...
Страница 263: ... 258 Service 19 HM T 340 Outdoor unit FDCW60VNX FDCW71VNX Component replacement ...
Страница 264: ...Service 259 19 HM T 340 FDCW100VNX FDCW140VNX LEK LEK Component replacement ...
Страница 290: ... 285 Components 19 HM T 340 Components ...
Страница 300: ... 295 Components 19 HM T 340 PT300 Component positions ...
Страница 301: ... 296 Components 19 HM T 340 Component positions PT300 PT300 A mm 1634 B mm 743 C mm 673 ...
Страница 302: ... 297 Components 19 HM T 340 PT500 Component positions ...
Страница 303: ... 298 Components 19 HM T 340 PT500 Component positions PT500 A mm 1835 B mm 897 C mm 832 ...
Страница 311: ...THo R THo A THo D Outside units FDCW60VNX 306 Components 19 HM T 340 Piping system ...