14 - 15 14 - 15
MELSEC
14 TROUBLESHOOTING
14.4.1 Flowchart to use when RUN LED is unlit
NO (The "RUN" LED has been off since the power was turned on.)
YES
NO (The "RUN" LED turned off
while communicating)
Did the LED turn
off even when communication
with other station was being
performed?
Is communication with
other station continued?
Replace the MELSECNET/H board
since the MELSECNET/H board's
"RUN" LED is broken.
Is there
a WDT (288) error log
1
remaining?
Did the "RUN"
LED turn on after replacing the
MELSECNET/H
board?
Check PC hardware, etc.
Lengthen the driver WDT monitoring time
(Refer to Section 14.7.)
Complete
An error occurs.
YES
NO
YES
YES
NO
1: WDT error logs can be checked on the event viewer. (Refer to 14.3.2)