[8-9 Troubleshooting Problems with Major Components on BC Controller ]
HWE18220_GB
chapter 8 -
37
8 Troubleshooting Based on Observed Symptoms
1) BC controller: Phenomena when LEV is connected wrongly (reverse connection of LEV1 and LEV3 or LEV4) to the board.
2) BC controller: Phenomena when LEV is connected wrongly (reverse connection of LEV3 and LEV4) to the board
3) Check method of fully open state or fully closed state of LEV
Check LEV opening (pulse) on the self-diagnosis LED (Outdoor control board SW1).
Full open: 3000 pulses
Fully closed: 41 pulses (In the case of heating-only mode, however, the pulse may become 41 or more.)
When LEV is fully open, measure the temperature at the upstream and downstream pipes of LEV, and make sure that there
is no temperature difference.
When LEV is fully closed, check that there is no refrigerant flowing sound.
Phenomena
Cooling-only
Cooling-main
Heating only
Heating main
Non-cooling
SH12 small, SC11 small
SC16 small, branch pipe
SC small
BC controller sound
Non-cooling and non-heating
SH12 small, SC11 small
SC16 large, but branch pipe
SC small
BC controller sound
PHM
large
Indoor heating SC small
PHM large
Non-cooling
Indoor heating SC small
PHM large
Phenomena
Cooling-only
Cooling-main
Heating only
Heating main
Non-cooling
SH12 large, SC11 small
SC16 small, branch pipe
SC small
Non-cooling
SH12 large, SC11 small
SC16 small, branch pipe SC
small
SH12 large
Non-cooling
SH12 large, SC16 small
Содержание PURY-HP144
Страница 1: ......
Страница 9: ...viii ...
Страница 13: ...HWE18220_GB ...
Страница 29: ...HWE18220_GB ...
Страница 77: ...HWE18220_GB ...
Страница 95: ...HWE18220_GB ...
Страница 125: ...HWE18220_GB ...
Страница 153: ...HWE18220_GB ...
Страница 163: ...HWE18220_GB ...
Страница 343: ...HWE18220_GB ...
Страница 361: ...HWE18220_GB ...
Страница 398: ......