[8-3 Refrigerant Control Problems ]
10
-
chapter 8
HWE18220_GB
8 Troubleshooting Based on Observed Symptoms
8-3
Refrigerant Control Problems
8-3-1
Units in the Cooling Mode Do Not Operate at Expected Capacity.
1. Phenomena
Although cooling operation starts with the normal remote controller display, the capacity is not enough.
2. Cause, check method and remedy
Cause
Check method and remedy
1.
Compressor frequency does not rise sufficiently.
Faulty detection of pressure sensor.
Protection works and compressor frequency does
not rise due to high discharge temperature
Protection works and compressor frequency does
not rise due to high pressure
Pressure drops excessively.
(1)
Check pressure difference between the detected
pressure by the pressure sensor and the actual pres-
sure with self-diagnosis LED.
ĺ
If the accurate pressure is not detected, check the
pressure sensor.
Refer to the following page(s). [8-5-1 Comparing the
High-Pressure Sensor Measurement and Gauge
Pressure]
Note:
Lower inlet pressure by the low pressure sensor than
the actual pressure causes insufficient capacity.
SW4 setting (SW6-10: OFF)
(2)
Check temperature difference between the evaporat-
ing temperature (Te) and the target evaporating tem-
perature (Tem) with self-diagnosis LED.
Note:
Higher Te than Tem causes insufficient capacity.
SW4 setting (SW6-10: OFF)
Note:
Protection works and compressor frequency does not
rise even at higher Te than Tem due to high discharge
temperature and high pressure.
At high discharge temperature:
Refer to the following page(s). [7-3-1 Error Code
[1102]]
At high pressure:
Refer to the following page(s). [7-3-3 Error Code
[1302] (during operation)]
2.
Indoor unit LEV malfunction
Refer to the following page(s).[8-8 Troubleshooting
LEV Problems]
Insufficient refrigerant flows due to LEV malfunc-
tion (not enough opening) or protection works and
compressor frequency does not rise due to pres-
sure drop.
Refrigerant leak from LEV on the stopping unit
causes refrigerant shortage on the running unit.
High pressure sensor
Low pressure sensor
SW4
SW4
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
Evaporating
temperature Te
Target evaporating
temperature Tem
SW4
SW4
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
Содержание PURY-HP144
Страница 1: ......
Страница 9: ...viii ...
Страница 13: ...HWE18220_GB ...
Страница 29: ...HWE18220_GB ...
Страница 77: ...HWE18220_GB ...
Страница 95: ...HWE18220_GB ...
Страница 125: ...HWE18220_GB ...
Страница 153: ...HWE18220_GB ...
Страница 163: ...HWE18220_GB ...
Страница 343: ...HWE18220_GB ...
Страница 361: ...HWE18220_GB ...
Страница 398: ......