[2-9 Example System with an MA and an ME Remote Controller ]
HWE18220_GB
28
-
chapter 2
2 Restrictions
2-9
Example System with an MA and an ME Remote Controller
2-9-1
System with a Connection of System Controller to Centralized Control
Transmission Line
(1) Sample control wiring
(2) Cautions
1) Be sure to connect a system controller.
2) ME remote controller and MA remote controller cannot both be con-
nected to the same group of indoor units.
3) Assign to the indoor units connected to the MA remote controller ad-
dresses that are smaller than those of the indoor units that are con-
nected to the ME remote controller.
4) No more than 2 ME remote controllers can be connected to a group
of indoor units.
5) No more than 2 MA remote controllers can be connected to a group
of indoor units.
6) Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
7) Replace the power jumper connector of the control board from CN41
to CN40 on only one of the outdoor units.
8) Provide an electrical path to ground for the S terminal on the terminal
block for centralized control on only one of the outdoor units.
9) When the number of the connected indoor units is as shown in the
table at right, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
The above table shows the number of transmission
boosters that is required by the system with three BC
controllers. For each BC controller added or subtracted,
subtract or add two indoor units.
Refer to the DATABOOK for further information about
how many booster units are required for a given system.
10) When a power supply unit is connected to the transmis-
sion line for centralized control, leave the power jumper
connector on CN41 as it is (factory setting).
IC
TB5
S
TB15
1 2
01
IC
TB5
S
TB15
1 2
02
IC
TB5
S
TB15
1 2
06
106
IC
TB5
S
TB15
1 2
05
A1 B2
MA
A1 B2
RC
A1 B2
MA
IC
TB5
S
1 2
TB15
IC
TB5
S
TB15
1 2
04
03
104
A1 B2
RC
OC
TB3
TB7
S
51
OS
TB3
TB7
S
52
OC
TB3
TB7
S
54
OS
TB3
TB7
S
55
L31
A B S
L32
SW5-1 OFF ON
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
Leave the male
connector on
CN41 as it is.
To be left
unconnected
To be left
unconnected
To be left
unconnected
To be connected
System controller
Note1
*1 When only the LM adapter is connected, leave SW5-1 to OFF (as it is).
*2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
S
BC
TB02
53
S
BC
TB02
56
L22
L21
L12
L11
SW5-1 OFF ON
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
Move the male connector
from CN41 to CN40.
Group
Group
Group
Group
M1M2
Number of transmission booster
(sold separately) required
1 unit
2 units
3 units
When the P72 and P96 models are
not included in the connected indoor
units
15 - 34
units
35 - 50
units
-
When the P72 and P96 models are
included in the connected indoor
units
11 - 26
units
27 - 42
units
43 - 50
units
Содержание PURY-HP144
Страница 1: ......
Страница 9: ...viii ...
Страница 13: ...HWE18220_GB ...
Страница 29: ...HWE18220_GB ...
Страница 77: ...HWE18220_GB ...
Страница 95: ...HWE18220_GB ...
Страница 125: ...HWE18220_GB ...
Страница 153: ...HWE18220_GB ...
Страница 163: ...HWE18220_GB ...
Страница 343: ...HWE18220_GB ...
Страница 361: ...HWE18220_GB ...
Страница 398: ......