[5-2 Outdoor Unit Control ]
HWE18220_GB
chapter 5 -
17
5 Control
5-2-8
Continuous heating mode control
(1) Continuous heating mode start conditions
Continuous heating mode will start when all the conditions listed in the table below are met (outside temperature, cumulative
compressor operation time, and piping temperature).
However, even when the conditions are met, after the maximum number of consecutive continuous heating operation shown
below is performed, the reverse defrost operation will be performed one time.
Maximum number of consecutive continuous heating operations
(2) Valve operation during Continuous heating cycle
1) When Single unit
Continuous heating operation is performed in the order shown below.
On a single unit model of HP72-HP144, defrosting is performed on the front and rear heat exchangers separately. Operation
patterns are shown in the table below.
Single unit
Combination units
Outside temperature
(TH7)
1.0°C [33.8°F]
TH7 < 7.0°C [44.6°F]
-5.0°C [23.0°F]
TH7 < 7.0°C [44.6°F]
Cumulative compressor
operation time
When 50 minutes have passed
When 50 minutes have passed
Piping temperature
(TH3)
TH7
í
10°C [50°F] < TH3 < 2.0°C [35.6°F]
TH7
í
10°C [50°F] < TH3 < 2.0°C [35.6°F]
7 times
Front HEX defrosting
Rear HEX defrosting
Outdoor unit fan 1
Stopped
Stopped
Outdoor unit fan 2
Stopped
Stopped
SV1a
OFF
SV2
OFF
LEV2a
200 3000
LEV2b
1500
400
LEV2c
-
LEV2d
6000
20
21S4a
OFF
ON
21S4b
ON
OFF
21S4c
-
Содержание PURY-HP144
Страница 1: ......
Страница 9: ...viii ...
Страница 13: ...HWE18220_GB ...
Страница 29: ...HWE18220_GB ...
Страница 77: ...HWE18220_GB ...
Страница 95: ...HWE18220_GB ...
Страница 125: ...HWE18220_GB ...
Страница 153: ...HWE18220_GB ...
Страница 163: ...HWE18220_GB ...
Страница 343: ...HWE18220_GB ...
Страница 361: ...HWE18220_GB ...
Страница 398: ......