[5-1 Dipswitch Functions and Factory Settings ]
2
-
chapter 5
HWE18220_GB
5 Control
SW7
1
Enables or disables
the detection of the
following types of in-
verter compressor er-
rors
ACCT, DCCT sensor
error(5301 Detail
code 115, 116)
ACCT, DCCT sensor
circuit error(5301 De-
tail code 117, 118)
IPM open-phase/
CNCT2 connection
error(5301 Detail
code 119)
Wiring connection er-
ror(5301 Detail code
120)
Error detection en-
abled
Error detection dis-
abled (no-load op-
eration allowed)
Any time after pow-
er on
C
2
Enables or disables
no-load operation of
the left fan inverter
The unit continues
no-load operation for
30 seconds and
comes to an error
stop. See the rele-
vant pages for de-
tails: [8-10-8
Checking the Fan
Board for Damage at
No Load]
No-load operation
disabled
No-load operation
enabled
Any time after pow-
er on
C
3
-
-
-
-
-
4
Enables or disables
no-load operation of
the right fan inverter
The unit continues
no-load operation for
30 seconds and
comes to an error
stop. See the rele-
vant pages for de-
tails: [8-10-8
Checking the Fan
Board for Damage at
No Load]
No-load operation
disabled
No-load operation
enabled
Any time after pow-
er on
C
5
-
-
-
-
-
6
-
-
-
-
-
7
-
-
-
-
-
8
-
-
-
-
-
9
Switches between
the normal startup
mode and the USB
writer rewrite mode
Normal startup
mode
USB writer rewrite
mode
Before power on
C
Switch
Function
Function according to switch setting
Switch setting tim-
ing
Units that require
switch setting
(Note 2)
OFF
ON
Содержание PURY-HP144
Страница 1: ......
Страница 9: ...viii ...
Страница 13: ...HWE18220_GB ...
Страница 29: ...HWE18220_GB ...
Страница 77: ...HWE18220_GB ...
Страница 95: ...HWE18220_GB ...
Страница 125: ...HWE18220_GB ...
Страница 153: ...HWE18220_GB ...
Страница 163: ...HWE18220_GB ...
Страница 343: ...HWE18220_GB ...
Страница 361: ...HWE18220_GB ...
Страница 398: ......