[5-2 Outdoor Unit Control ]
HWE18220_GB
chapter 5 -
15
5 Control
(2) Defrost operation
* When PWFY-AU model units are connected, SVA and SVC on the BC should be set to ON.
* On the module system, both outdoor units start in the defrost mode regardless of the operation mode before the defrost
operation.
* The compressor frequency is fixed at 60Hz for 3 minutes.
* The compressor frequency is fixed at 60Hz when the compressor bottom SH (TH15 - Te)
10ºC [18ºF].
Outdoor unit
Compressor frequency
Model
Compressor frequency
HP72 model
107Hz
HP96, HP120 models
121Hz
Outdoor unit fan
Stopped
SV1a
ON (open)
LEV2a, 2b
3000
LEV2d
20
LEV4
0
LEV9
480
21S4a, 21S4b
OFF
SV2
OFF (closed), ON (open)
BC controller
LEV1
J type: 3000, JA type: 3000, KA type: 3000
LEV3(a)
J type: 3000, JA type: 3000,
KA type: 3000, KB type: 60 (full closed)
LEV4 (JA and KA types
only)
JA type: 3000, KA type: 3000
SVM1 (JA and KA types
only)
ON
SVM1b (JA and KA types
only)
ON
SVB
OFF
SVA
Ports that are connected to the indoor units in cooling Thermo-ON
Other ports: OFF