[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
52
-
chapter 7
HWE18220_GB
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
(2) Troubleshooting problems for indoor units (B)
Cause
Check method and remedy
(1)
When the power supply unit for transmission lines is used
and the male power supply connector is connected to the
female power supply switch connector (CN40) for the
transmission line for centralized control
1)
Check voltage of the transmission line for central-
ized control.
20 V or more: Check (1) on the left.
Less than 20 V: Check (2) on the left.
(2)
Disconnection or shutdown of the power source of the
power supply unit for transmission line
(3)
System controller (MELANS) malfunction
2)
Check the causes of the error in items (1) through
(3) in the "Cause" column.