5
OCH675E
Cautions for refrigerant piping work
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same
as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working
pressure of R410A is 1.6 times higher than that of R22, their sizes of flared sections and flare nuts are different.
1
Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness
shown below. (Never use pipes of 0.7 mm or below.)
Diagram below: Piping diameter and thickness
Nominal
dimensions (in)
Outside
diameter (mm)
Thickness (mm)
R410A
R22
1/4
6.35
0.8
0.8
3/8
9.52
0.8
0.8
1/2
12.70
0.8
0.8
5/8
15.88
1.0
1.0
3/4
19.05
1.0*
1.0
7/8
22.2
1.0*
1.0
* Use 1/2 H or H pipes.
2
Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that,
R410A is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refrig
-
erants. Therefore, to enhance airtightness and strength, flare cutting dimension of copper pipe for R410A has been
specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A
also has partly been changed to increase strength as shown below. Set copper pipe correctly referring to copper pipe
flaring dimensions for R410A below. For 1/2 and 5/8 inch pipes, the dimension B changes.
Use torque wrench corresponding to each dimension.
Dimension A
Dimension B
Flare cutting dimensions
Nominal
dimensions (in)
Outside
diameter (mm)
Dimension A ( )(mm)
R410A
R22
1/4
6.35
9.1
9.0
3/8
9.52
13.2
13.0
1/2
12.70
16.6
16.2
5/8
15.88
19.7
19.4
3/4
19.05
—
23.3
+0
-0.4
Flare nut dimensions
Nominal
dimensions (in)
Outside
diameter (mm)
Dimension B(mm)
R410A
R22
1/4
6.35
17.0
17.0
3/8
9.52
22.0
22.0
1/2
12.70
26.0
24.0
5/8
15.88
29.0
27.0
3/4
19.05
—
36.0
3
Tools for R410A (The following table shows whether conventional tools can be used or not.)
Tools and materials
Use
R410A tools
Can R22 tools be used?
Can R407C tools be used?
Gauge manifold
Air purge, refrigerant charge
and operation check
Tool exclusive for R410A
Charge hose
Tool exclusive for R410A
Gas leak detector
Gas leak check
Tool for HFC refrigerant
Refrigerant recovery equipment Refrigerant recovery
Tool exclusive for R410A
Refrigerant cylinder
Refrigerant charge
Tool exclusive for R410A
Applied oil
Apply to flared section
Ester oil, ether oil and
alkylbenzene oil
(minimum amount)
Ester oil, ether oil:
Alkylbenzene oil: minimum amount
Safety charger
Prevent compressor malfunction
when charging refrigerant by
spraying liquid refrigerant
Tool exclusive for R410A
Charge valve
Prevent gas from blowing out
when detaching charge hose
Tool exclusive for R410A
Vacuum pump
Vacuum drying and air
purge
Tools for other refrigerants
can be used if equipped with
adopter for reverse flow check
(Usable if equipped with
adapter for reverse flow)
(Usable if equipped with
adapter for reverse flow)
Flare tool
Flaring work of piping
Tools for other refrigerants can be
used by adjusting flaring dimension
(Usable by adjusting
flaring dimension)
(Usable by adjusting
flaring dimension)
Bender
Bend the pipes
Tools for other refrigerants can be used
Pipe cutter
Cut the pipes
Tools for other refrigerants can be used
Welder and nitrogen gas cylinder Weld the pipes
Tools for other refrigerants can be used
Refrigerant charging scale Refrigerant charge
Tools for other refrigerants can be used
Vacuum gauge or
thermistor vacuum gauge
and vacuum valve
Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and
refrigerant to thermistor vacuum gauge)
Tools for other refrigerants
can be used
Charging cylinder
Refrigerant charge
Tool exclusive for R410A
─
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.