102
OCH675E
Check method of DC fan motor (fan motor/outdoor multi controller circuit board)
1
Notes
· High voltage is applied to the connector (CNF1, 2) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNF1, 2) for the motor with the power supply on.
(It causes trouble of the outdoor multi controller circuit board and fan motor.)
2
Self check
Symptom: The outdoor fan cannot rotate.
Correct the wiring.
Replace the outdoor multi
controller circuit board (MULTI.B.).
Is the fan motor
normal?
Yes
Yes
Yes
Yes
Yes
No
Fail
Fail
OK
OK
No
No
No
Fuse check
Check the fuse (F500) on outdoor
multi controller circuit board.
Replace the outdoor multi
controller circuit board (MULTI.B.)
and the defective fan motor.
Disconnect the FAN motor connector and
measure the resistance of connector pins.
Refer to “8-7. HOW TO CHECK THE PARTS”.
Wiring contact check
Contact of fan motor connector
(CNF1,2)
Did the fuse blow?
Is there contact failure?
Is the voltage normal?
Replace the defective fan motor.
Replace the outdoor multi
controller circuit board.
Check the operation.
Complete.
Complete.
Replace the defective fan motor.
Replace the outdoor multi
controller circuit board.
Check the operation of fan.
Power supply check (Remove the connector (CNF1,2))
1
While the breaker is OFF, disconnect the compressor wirings (U/V/W) from the outdoor power circuit board.
2
While the breaker is OFF, disconnect the fan motor connector CNF1,2.
3
When 5 minutes have passed since turning ON the breaker, turn SW7-1 ON.
4
Check the voltage of the outdoor multi controller circuit board.
Measure the voltage in the outdoor controller circuit board.
TEST POINT 1 : VDC (between 1 (+) and 4 (−) of the fan connector): 310–340 V DC (Y)
: VDC (between 1 (+) and 4 (−) of the fan connector): 310-340 V DC (when PAM stops), 380 V DC (when PAM is operating) (V)
TEST POINT 2 : VCC (between 5 (+) and 4 (−) of the fan connector): VCC 15 V DC
TEST POINT 3 : VCC (between 6 (+) and 4 (−) of the fan connector): VCC 0–6.5 V DC
Note: Turn SW7-1 OFF after the troubleshooting completes.