Permissible Lengths
Constraint items
Longest transmission cable length:
L
1
+ L
2
[
200 m (1.25 mm²)
MA remote controller cable length:
R
1
,
R
2
[
200 m (0.3 to 1.25 mm²)
NO
TB5
TB15
TB3
TB7
(00)
OC
TB5
TB15
(00)
M-IC
MA-RC
MA-RC
M-NET RC
1 2
A B
M1 M2 S
M1 M2 S
M1 M2 S
1 2
M1 M2 S
A B
A B
(00)
M-IC
Longest transmission cable length:
L
1
+ L
2
[
200 m (1.25 mm²)
MA remote controller cable length:
R
3
+
R
4
,
R
5
[
200 m
(0.3 to 1.25 mm²)
MA-RC
TB5
TB15
(00)
M-IC
TB3
TB7
(00)
OC
TB5
TB15
(00)
M-IC
MA-RC
MA-RC
MA-RC
MA-RC
1 2
M1 M2 S
M1 M2 S
M1 M2 S
A B
A B
A B
A B
1 2
M1 M2 S
NO
A B
Longest transmission cable length:
L
1
+ L
2
[
200m (1.25 mm²)
MA remote controller cable length:
R
6
+
R
7
[
200 m (0.3 to 1.25 mm²)
NO
MA-RC
(00)
M-IC
(00)
OC
MA-RC
(00)
M-IC
TB5
1 2
TB15
A B
M1 M2
TB3
S
TB7
TB5
TB15
M1 M2 S
M1 M2 S
1 2
M1 M2 S
A B
The MA remote controller and the M-NET remote controller cannot be used together
with the indoor unit of the same group.
3 MA remote controllers or more cannot be connected with the indoor unit of the
same group.
The second MA remote controller is connected with the terminal block (TB15) for the
MA remote controller of the same indoor unit (M-IC) as the first remote control.