28
OCH675E
7-3-3. Mixed system (CITY MULTI indoor units and M, S, P series indoor units (Via Branch box)
System pipe size
Branch box pipe size
Pipe size
A
Liquid pipe
Gas pipe
L1
[
60 m and L2
[
20 m
ø9.52 mm
ø19.05 mm
L1 > 60 m or L2 > 20 m
ø12.7 mm
ø19.05 mm
B, C, D, E
Total capacity
of indoor
units
Liquid pipe (mm)
Gas pipe
–
16.0 kW
L1
[
60 m or L2
[
20 m
ø9.52
ø15.88
mm
L1 > 60 m or L2 > 20 m
ø12.7
16.1
–
29.1 kW
L1
[
60 m or L2
[
20 m
ø9.52
ø19.05
mm
L1 > 60 m or L2 > 20 m
ø12.7
L1: The farthest piping length from the outdoor unit to an indoor unit.
L2: The farthest piping length for the main pipes from the outdoor
unit to the branch box.
•
The line-up of a connectable indoor unit depends on a district/areas/country.
a,b,c – j
Indoor unit series Model number Liquid pipe
Gas pipe
CITY MULTI
– 50
ø6.35 mm
ø12.7
mm
63 – 140
ø9.52 mm
ø15.88
mm
200
ø9.52 mm
ø19.05
mm
M series or
S series
– 42
ø6.35 mm
ø9.52 mm
50
ø6.35 mm
ø12.7
mm
60
ø6.35 mm
ø15.88
mm
71 –
ø9.52 mm
ø15.88
mm
P series
– 50
ø6.35 mm
ø12.7
mm
60 –
ø9.52 mm
ø15.88
mm
Note:
When using 35, 50 type indoor unit of P series, use the flare nut attached
to the indoor unit.
Do not use the flare nut in the indoor unit accessory. If it is used, a gas
leakage or even a pipe extraction may occur.
2-branch joint
CMY-Y62-G-E
4-branch header
CMY-Y64-G-E
8-branch header
CMY-Y68-G-E
Different-diameter joint (optional parts)
Model name
Connected pipes
diameter
Diameter A Diameter B
mm
mm
mm
MAC-A454JP-E
ø9.52 → ø12.7
ø9.52
ø12.7
MAC-A455JP-E
ø12.7 → ø9.52
ø12.7
ø9.52
MAC-A456JP-E
ø12.7 → ø15.88
ø12.7
ø15.88
PAC-493PI
ø6.35 → ø9.52
ø6.35
ø9.52
PAC-SG76RJ-E
ø9.52 → ø15.88
ø9.52
ø15.88
PAC-SG75RJ-E
ø15.88 → ø19.05
ø15.88
ø19.05
2-branch pipe (Joint): Optional parts (According to the connection
method, you can choose the favorite one.)
Model name
Connection method
MSDD-50AR-E
flare
MSDD-50BR-E
brazing
■ Installation procedure
Refer to the installation manual of optional parts.
A
A
E
B
C
C
D
D
a
b
c
d
e
f
g
h
i
j
E
E
E
E
E
F
F
F
F
F
A
Outdoor Unit
B
First joint
C
Branch header
D
Branch box
E
CITY MULTI Indoor unit
F
M, S, P series Indoor unit
L
1
L
2
B
Branch box
Port A
Port B
Port C
Port D
Port E
(1) Valve size of branch box for outdoor unit
For liquid
ø9.52 mm
For gas
ø15.88 mm
(2) Valve size of branch box for indoor unit
A
UNIT Liquid pipe ø6.35 mm
Gas pipe
ø9.52 mm
B
UNIT Liquid pipe ø6.35 mm
Gas pipe
ø9.52 mm
C
UNIT Liquid pipe ø6.35 mm
Gas pipe
ø9.52 mm
D
UNIT Liquid pipe ø6.35 mm
Gas pipe
ø9.52 mm
E
UNIT Liquid pipe ø6.35 mm
Gas pipe
ø12.7 mm
Note: 3-branch type: only
A
,
B
,
C
unit