120
OCH675E
9-3. DESIGN FOR CONTROL WIRING
Please note that the types and numbers of control wires needed by CITY MULTI series will depend on the remote con
-
trollers and whether they are linked with the system.
9-3-1. Selection number of control wires
Use
M-NET remote controller
Remote controller used in system control operations
• Group operation involving different refrigerant systems
• Linked operation with upper control system
Remote controller → indoor unit
2-core wires (non-polar)
Transmission
wires
Wires connecting → indoor units
Wires connecting → indoor units with outdoor unit
Wires connecting → outdoor units
9-4. WIRING TRANSMISSION CABLES
9-4-1. Types of control cables
1. Wiring transmission cables
Types of transmission cables
Shielding wire (2-core) CVVS, CPEVS or MVVS
Cable diameter
More than 1.25 mm
2
Maximum wiring length
Within 200 m
2. M-NET Remote control cables
Types of remote control cables
Shielding wire (2-core) CVVS, CPEVS, or MVVS
Cable diameter
0.5 to 1.25 mm
2
Remarks
When 10 m is exceeded, use a cable with the same specifications
as transmission line wiring.
3. MA Remote control cables
Type of remote control cable
Sheathed 2-core cable (unshielded) CVV
Cable diameter
0.3 to 1.25 mm
2
(0.75 to 1.25 mm
2
)*
Remarks
Within 200 m
* Connected with simple remote controller.
9-4-2. Wiring examples
•
Controller name, symbol and allowable number of controllers.
Name
Symbol
Allowable number of controllers
Outdoor unit controller
OC
―
Indoor unit
controller
CITY MULTI
series
M-IC
1 to 12 units per 1 OC *
1
M, S, P
series
A-IC
2 to 8 units per 1 OC *
1
Branch box
BC
0 to 2 units per 1 OC
Remote
controller
M-NET
M-NET RC *
2
Maximum of 12 controllers for 1 OC
(Cannot be connected if the branch box is used.) *
1
MA
MA-RC
Maximum of 2 per group
Wireless
WL-RC
―
Note:
*1. The number of connectable units may be limited by some conditions such as an indoor unit’s capacity or each unit’s equivalent power consumption.
*2. Don’t use the Lossnay controller (PZ-61DR-E, PZ-43SMF-E, PZ-52SF-E, PZ-60DR-E).