background image

2

1.3. Before electric work

 Caution:

•  Be sure to install circuit breakers. If not installed, electric shock may result.

•  Please follow applicable federal, state, or local codes to prevent potential 

leakage/electric shock. Or install a ground fault interrupt for the prevention 

of leakage and electric shock.

•  For the power lines, use standard cables of sufficient capacity. Otherwise, a 

short circuit, overheating, or fire may result.

•  When installing the power lines, do not apply tension to the cables. If the 

connections are loosened, the cables can snap or break and overheating or 

fire may result.

•  Be sure to ground the unit. Do not connect the ground wire to gas or water 

pipes, lightning rods, or telephone grounding lines. If the unit is not prop-

erly grounded, electric shock may result.

•  Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), 

and molded case circuit breaker) with the specified capacity. If the circuit 

breaker capacity is larger than the specified capacity, breakdown or fire 

may result.

1.4. Before starting the test run

 Caution:

•  Turn on the main power switch more than 12 hours before starting operation.

  Starting operation just after turning on the power switch can severely damage 

the internal parts. Keep the main power switch turned on during the operation 

season.

•  Before starting operation, check that all panels, guards and other protective 

parts are correctly installed. Rotating, hot, or high voltage parts can cause 

injuries.

•  Do not touch any switch with wet hands. Electric shock may result.

•  Do not touch the refrigerant pipes with bare hands during operation. The 

refrigerant pipes are hot or cold depending on the condition of the flowing 

refrigerant. If you touch the pipes, burns or frostbite may result.

•  After stopping operation, be sure to wait at least 5 minutes before turning off 

the main power switch. Otherwise, water leakage or breakdown may result.

1.5. Using R410A refrigerant air conditioners

 Caution:

•  Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, 

to connect the refrigerant pipes. Make sure the insides of the pipes are clean 

and do not contain any harmful contaminants such as sulfuric compounds, 

oxidants, debris, or dust. Use pipes with the specified thickness. (Refer to 

page 5) Note the following if reusing existing pipes that carried R22 refrigerant.

-  Replace the existing flare nuts and flare the flared sections again.

-  Do not use thin pipes. (Refer to page 5)

•  Store the pipes to be used during installation indoors and keep both ends of 

the pipes sealed until just before brazing. (Leave elbow joints, etc. in their 

packaging.) If dust, debris, or moisture enters the refrigerant lines, oil dete-

rioration or compressor breakdown may result.

•  Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration 

oil applied to the flared sections. If mineral oil is mixed in the refrigeration 

oil, oil deterioration may result.

•  Do not use refrigerant other than R410A refrigerant. If another refrigerant is 

used, the chlorine will cause the oil to deteriorate.

1.6. Precautions for salt damage–resistant model  

(“-BS” model)

Although this product (only “-BS” model) has been designed to be resistant to salt 

damage, observe the following precautions to maintain the performance of the unit.

1. Avoid installing the unit in a location where it will be exposed directly to seawater 

or sea breeze.

2. If the cover panel may become covered with salt, be sure to install the unit in a 

location where the salt will be washed away by rainwater. (If a sunshade is installed, 

it may be difficult for rainwater to clean the panel.)

3. To ensure that water does not collect in the base of the outdoor unit, make sure 

that the base is level, not at angle. Water collecting in the base of the outdoor unit 

could cause rust.

•  Use the following tools specifically designed for use with R410A refrigerant.

  The following tools are necessary to use R410A refrigerant. Contact your 

nearest dealer for any questions.

Tools (for R410A)  

Gauge manifold 

Flare tool 

Charge hose 

Size adjustment gauge 

Gas leak detector 

Vacuum pump adapter 

Torque wrench 

Electronic refrigerant charging scale 

•  Be sure to use the correct tools. If dust, debris, or moisture enters the refriger-

ant lines, refrigeration oil deterioration may result.

•  Do not use a charging cylinder. If a charging cylinder is used, the composition 

of the refrigerant will change and the efficiency will be lowered.

1. Safety precautions

4. If the unit is installed in a coastal area, clean the unit with water regularly to remove 

any salt build-up.

5. If the unit is damaged during installation or maintenance, be sure to repair it.

6. Be sure to check the condition of the unit regularly.

7. Be sure to install the unit in a location with good drainage.

en

RG79F368H02_EN.indd   2

2019/11/18   15:57:10

003

Содержание PUMY-HP36NKMU1

Страница 1: ...ccident et vous assurer d une utilisation correcte MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado Français Español English Air Conditioners OUTDOOR UNIT PUMY P36 48 60NKMU3 BS PUMY HP36 48NKMU1 Français Español English Français Español English HFC utilized R410A FOR INSTALLER POUR L INSTALLATEUR PARA...

Страница 2: ...or unit use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pres sure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will...

Страница 3: ...pipes that carried R22 refrigerant Replace the existing flare nuts and flare the flared sections again Do not use thin pipes Refer to page 5 Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing Leave elbow joints etc in their packaging If dust debris or moisture enters the refrigerant lines oil dete rioration or compressor breakdow...

Страница 4: ...outdoor unit Number of units that can be connected Capacity range of connected units PUMY P36NKMU3 36 kBtu h 1 11 units 18 46 8 kBtu h PUMY HP36NKMU1 PUMY P48NKMU3 48 kBtu h 1 12 units 24 62 4 kBtu h PUMY HP48NKMU1 PUMY P60NKMU3 60 kBtu h 1 12 units 30 78 0 kBtu h Table 2 Rated capacity cooling of the indoor units Indoor unit type P04 P05 P06 P08 P12 P15 P18 P24 P30 P36 P48 P54 P72 Rated capacity ...

Страница 5: ...tional air outlet guides for upward airflow 2 5 3 When installing multiple outdoor units Leave 1 25 mm space or more between the units 1 Obstacles at rear Fig 2 11 2 Obstacles at rear and above Fig 2 12 No more than 3 units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front Fig 2 13 When using the op...

Страница 6: ... with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil ap plied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to con nect the refrigerant pipes Use refrigerant pipes with the thicknesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful conta...

Страница 7: ...thickness Excessive thickness may cause incorrect installation of the indoor unit and lack of thickness may cause dew drippage Warning When pumping down the refrigerant stop the compressor before disconnect ing the refrigerant pipes The compressor may burst and cause injury if any foreign substance such as air enters the system A Outdoor Unit B First Branch C Indoor unit D Cap A Outdoor Unit B Fir...

Страница 8: ...ssor Abnormal noise or vibration may result 1Pipes must be connected starting from the indoor unit Flare nuts must be tightened with a torque wrench 2Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil Ap plied on site When usual pipe sealing is used refer to Table 2 for flaring of R410A refrigerant pipes The size adjustment gauge can be used to confirm A measurements ...

Страница 9: ...otectively wrapped up to a diameter of ø90 mm 3 9 16 before or after connecting the pipes Cut out the knockout in the pipe cover following the groove and wrap the pipes Pipe inlet gap Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result Note Triple Evacuatio...

Страница 10: ...52 Total capacity of connected indoor units Amount for the indoor units P36 48 HP36 48 m 19 0 g m ft 0 21 oz ft P36 48 HP36 48 m 50 0 g m ft 0 55 oz ft 27 1 5 kg 53 oz 28 54 2 5 kg 88 oz P60 m 27 0 g m ft 0 29 oz ft P60 m 70 0 g m ft 0 75 oz ft 55 3 0 kg 106 oz Included refrigerant amount when shipped from the factory Included refrigerant amount P36 48 HP36 48 4 8 kg 169 oz P60 5 1 kg 180 oz 4 7 A...

Страница 11: ...nsmission terminal block TB3 is connected to the ground C when the unit is shipped from the factory 2 Conduit mounting plates are being provided Remove the knock out pieces from the piping cover pass the power supply and transmission wires through the appropriate knock out holes and connect the wires to the terminal block 3 Fix power source wiring to terminal box by using buffer bushing for tensil...

Страница 12: ...4 A P60 8 4 AWG8 8 4 AWG8 3 4 inch 40 A 40 A 30 mA 0 1 sec or less 36 A 45 A Indoor Unit Refer to installation manual of indoor unit 1 Please follow applicable federal state or local codes to prevent potential leakage electric shock Or install a ground fault interrupt for the prevention of leakage and electric shock IMPORTANT If a current leakage breaker is used it should be compatible with higher...

Страница 13: ...xternal force is imparted to terminal connections If connections are not fixed firmly it may cause heating or fire Be sure to use the appropriate type of overcurrent protection switch Note that generated overcurrent may include some amount of direct current Turn on main power when the ambient temperature is 20 C 4 F or higher In below 20 C 4 F it needs at least 12hr stand by before the units opera...

Страница 14: ...ops due to accumulation of refrigerant in the compressor The resistance will rise above 1 MΩ after the compressor is warmed up for 12 hours The time necessary to warm up the compressor varies according to atmos pheric conditions and refrigerant accumulation To operate the compressor with refrigerant accumulated in the compressor the compressor must be warmed up at least 12 hours to prevent breakdo...

Страница 15: ...lected by switching the DIP switch 9 2 on outdoor controller board It is possible to set it to the following power consumption compared with ratings by setting SW1 2 Outdoor controller board DIP SW9 2 SW1 SW2 Function Silent mode OFF ON Silent mode operation Demand control ON OFF OFF 100 Normal ON OFF 75 ON ON 50 OFF ON 0 Stop A Remote control panel B Relay circuit C External input adapter PAC SC3...

Страница 16: ...produire Lors de l installation du déplacement ou de l entretien de l appareil extérieur n utilisez que le réfrigérant spécifié R410A pour remplir les tuyaux de réfrigérant Ne pas le mélanger avec un autre réfrigérant et faire le vide d air dans les tuyaux Siduréfrigérantestmélangéavecdel air celapeutprovoquerdespointesdepression dans les tuyaux de réfrigérant et entraîner une explosion et d autre...

Страница 17: ...ns suivantes en cas de réutilisation de tuyaux de réfrigérant R22 existants Remplacer les écrous évasés existants et évaser de nouveau les sections évasées Ne pas utiliser de tuyaux fins Se reporter à la page 5 Stocker à l intérieur les tuyaux à utiliser pendant l installation et couvrir les deux extrémités jusqu au processus de brasage Laisser les joints de coude etc dans leur emballage L infiltr...

Страница 18: ...ur Capacité de l appareil extérieur Nombre d appa reils pouvant être raccordés Plage de capaci tés des appareils raccordés PUMY P36NKMU3 36 kBtu h 1 11 appareils 18 46 8 kBtu h PUMY HP36NKMU1 PUMY P48NKMU3 48 kBtu h 1 12 appareils 24 62 4 kBtu h PUMY HP48NKMU1 PUMY P60NKMU3 60 kBtu h 1 12 appareils 30 78 0 kBtu h Tableau 2 Capacité nominale refroidissement des appareils intérieurs Type d appareil ...

Страница 19: ... air en option pour un débit d air vers le haut 2 5 3 Lors de l installation de plusieurs appareils extérieurs Espacer les appareils de 1 25 mm minimum 1 Obstacles à l arrière Fig 2 11 2 Obstacles à l arrière et au dessus Fig 2 12 Ne pas installer côte à côte plus de trois appareils Espacer également les appareils comme illustré Ne pas utiliser les guidages de sortie d air en option pour un débit ...

Страница 20: ...age 2 pour les consignes non reprises ci dessous concernant l utilisation de climatiseurs avec un réfrigérant R410A Appliquer une petite quantité d huile ester éther ou alkylbenzène comme huile réfrigérante sur les sections évasées Utiliser le cuivre phosphoreux C1220 pour des tuyaux sans soudure en cuivre et en alliage de cuivre pour raccorder les tuyaux de réfrigérant Utiliser les tuyaux de réfr...

Отзывы: